petroska
There are no macros links in this template.
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Present Current Demand [Phase A] | <p>Host Meter Present Demand Current Units =A (Amps)</p> | SNMP agent |
cdPresentCurrentDemandL1<p>Update: 30s</p> |
Line B to Neutral | <p>Host Meter Voltage Line B to Neutral Units =V (Volts)</p> | SNMP agent |
vVbn<p>Update: 30s</p> |
Peak Current Demand [Phase B] | <p>-</p> | SNMP agent |
cdPeakCurrentDemandL2<p>Update: 30s</p> |
3 Phase Load Average | <p>Host Meter Load Current 3 Phase Average Units =A (Amps)</p> | SNMP agent |
lcIAvg<p>Update: 30s</p> |
Apparent Energy | <p>-</p> | SNMP agent |
eApparentEnergy<p>Update: 30s</p> |
Apparent power | <p>Host Meter Apparent Power Units =kVA</p> | SNMP agent |
pApparent<p>Update: 30s</p> |
Serial number | <p>Host meter 32 bit Serial Number</p> | SNMP agent |
midSerialNumber<p>Update: 3600</p> |
Line A to Line B | <p>Host Meter Voltage Line A to Line B Units =V (Volts)</p> | SNMP agent |
vVab<p>Update: 30s</p> |
Peak Current Demand [Phase C] | <p>-</p> | SNMP agent |
cdPeakCurrentDemandL3<p>Update: 30s</p> |
Line C to Neutral | <p>Host Meter Voltage Line C to Neutral Units =V (Volts)</p> | SNMP agent |
vVcn<p>Update: 30s</p> |
Firmware Version | <p>Host Meter Firmware Version</p> | SNMP agent |
midFirmwareVersion<p>Update: 3600</p> |
Real power | <p>Host Meter Real Power Units =kW</p> | SNMP agent |
pReal<p>Update: 30s</p> |
Reactive Energy | <p>Host Meter Reactive Energy Units =kVARh</p> | SNMP agent |
eReactiveEnergy<p>Update: 30s</p> |
Voltage Line to Neutral 3 Phase Average | <p>-</p> | SNMP agent |
vVlnAvg<p>Update: 30s</p> |
Device Name | <p>Host Meter Label plus Nameplate</p> | SNMP agent |
midDeviceName<p>Update: 3600</p> |
Line C to Line A | <p>Host Meter Voltage Line C to Line A Units =V (Volts)</p> | SNMP agent |
vVca<p>Update: 30s</p> |
Power factor | <p>Host Meter 3 Phase Total Power Factor</p> | SNMP agent |
pfPowerFactorTotal<p>Update: 30s</p> |
Peak Current Date [Phase A] | <p>Host Meter Peak Current Demand Date and Time</p> | SNMP agent |
cdPeakDateTimeL1<p>Update: 30s</p> |
Real Energy | <p>Host Meter Real Energy Units =kWh</p> | SNMP agent |
eRealEnergy<p>Update: 30s</p> |
Peak Current Date [Phase C] | <p>-</p> | SNMP agent |
cdPeakDateTimeL3<p>Update: 30s</p> |
Line to Line Average Voltage | <p>Host Meter Voltage Line to Line Average Voltage Units =V (Volts)</p> | SNMP agent |
vVllAvg<p>Update: 30s</p> |
Model Number | <p>Host Meter Model Number</p> | SNMP agent |
midModelNumber<p>Update: 3600</p> |
Phase A Load | <p>Host Meter Load Current Phase A Units =A (Amps)</p> | SNMP agent |
lcIa<p>Update: 30s</p> |
Power factor description | <p>Describes the current power factor Lead/Lag for IEEE mode Cap/Ind for IEC mode</p> | SNMP agent |
pfPowerFactorDescription<p>Update: 3600</p> |
Line B to Line C | <p>Host Meter Voltage Line B to Line C Units =V (Volts)</p> | SNMP agent |
vVbc<p>Update: 30s</p> |
Phase B Load | <p>Host Meter Load Current Phase B Units =A (Amps)</p> | SNMP agent |
lcIb<p>Update: 30s</p> |
Frequency | <p>Host Meter Frequency Units =Hz</p> | SNMP agent |
fFrequency<p>Update: 30s</p> |
Present Current Demand [Phase B] | <p>-</p> | SNMP agent |
cdPresentCurrentDemandL2<p>Update: 30s</p> |
Reactive power | <p>Host Meter Reactive Power Units =kVAR</p> | SNMP agent |
pReactive<p>Update: 30s</p> |
Peak Current Date [Phase B] | <p>-</p> | SNMP agent |
cdPeakDateTimeL2<p>Update: 30s</p> |
Line A to Neutral | <p>Host Meter Voltage Line A to Neutral Units =V (Volts)</p> | SNMP agent |
vVan<p>Update: 30s</p> |
Phase C Load | <p>Host Meter Load Current Phase C Units =A (Amps)</p> | SNMP agent |
lcIc<p>Update: 30s</p> |
Present Current Demand [Phase C] | <p>-</p> | SNMP agent |
cdPresentCurrentDemandL3<p>Update: 30s</p> |
Wiring Type | <p>Single Phase Line to Neutral 2 Wire 1CT 1PT is ‘10’ Single Phase Line to Line 2 Wire 1CT 1PT is ‘11’ Single Phase 3-Wire 3 wire 2CT 2PT is ‘12’ Three Phase 3 Wire 2CT 2PT is ‘30’ Three Phase 3 Wire 3CT 2PT is ‘31’ Three Phase 3 Wire 1CT 2PT is ‘32’ Three Phase 4 Wire 3CT 3PT is ‘40’ Three Phase 4 Wire 3CT 2PT is ‘42’ Three Phase 4 Wire 1CT 3PT is ‘44’</p> | SNMP agent |
swtWiringType<p>Update: 3600</p> |
Peak Current Demand [Phase A] | <p>Host Meter Peak Current Demand Units =A (Amps)</p> | SNMP agent |
cdPeakCurrentDemandL1<p>Update: 30s</p> |
There are no triggers in this template.
petroska
There are no macros links in this template.
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Present Current Demand [Phase B] | <p>-</p> | SNMP agent |
cdPresentCurrentDemandL2<p>Update: 30s</p> |
Present Current Demand [Phase A] | <p>Host Meter Present Demand Current Units =A (Amps)</p> | SNMP agent |
cdPresentCurrentDemandL1<p>Update: 30s</p> |
Peak Current Demand [Phase B] | <p>-</p> | SNMP agent |
cdPeakCurrentDemandL2<p>Update: 30s</p> |
Wiring Type | <p>Single Phase Line to Neutral 2 Wire 1CT 1PT is ‘10’ Single Phase Line to Line 2 Wire 1CT 1PT is ‘11’ Single Phase 3-Wire 3 wire 2CT 2PT is ‘12’ Three Phase 3 Wire 2CT 2PT is ‘30’ Three Phase 3 Wire 3CT 2PT is ‘31’ Three Phase 3 Wire 1CT 2PT is ‘32’ Three Phase 4 Wire 3CT 3PT is ‘40’ Three Phase 4 Wire 3CT 2PT is ‘42’ Three Phase 4 Wire 1CT 3PT is ‘44’</p> | SNMP agent |
swtWiringType<p>Update: 3600</p> |
Line A to Line B | <p>Host Meter Voltage Line A to Line B Units =V (Volts)</p> | SNMP agent |
vVab<p>Update: 30s</p> |
Reactive power | <p>Host Meter Reactive Power Units =kVAR</p> | SNMP agent |
pReactive<p>Update: 30s</p> |
Peak Current Demand [Phase A] | <p>Host Meter Peak Current Demand Units =A (Amps)</p> | SNMP agent |
cdPeakCurrentDemandL1<p>Update: 30s</p> |
Apparent power | <p>Host Meter Apparent Power Units =kVA</p> | SNMP agent |
pApparent<p>Update: 30s</p> |
Present Current Demand [Phase C] | <p>-</p> | SNMP agent |
cdPresentCurrentDemandL3<p>Update: 30s</p> |
Reactive Energy | <p>Host Meter Reactive Energy Units =kVARh</p> | SNMP agent |
eReactiveEnergy<p>Update: 30s</p> |
Real Energy | <p>Host Meter Real Energy Units =kWh</p> | SNMP agent |
eRealEnergy<p>Update: 30s</p> |
Power factor description | <p>Describes the current power factor Lead/Lag for IEEE mode Cap/Ind for IEC mode</p> | SNMP agent |
pfPowerFactorDescription<p>Update: 3600</p> |
Model Number | <p>Host Meter Model Number</p> | SNMP agent |
midModelNumber<p>Update: 3600</p> |
Power factor | <p>Host Meter 3 Phase Total Power Factor</p> | SNMP agent |
pfPowerFactorTotal<p>Update: 30s</p> |
Line to Line Average Voltage | <p>Host Meter Voltage Line to Line Average Voltage Units =V (Volts)</p> | SNMP agent |
vVllAvg<p>Update: 30s</p> |
Serial number | <p>Host meter 32 bit Serial Number</p> | SNMP agent |
midSerialNumber<p>Update: 3600</p> |
Line B to Neutral | <p>Host Meter Voltage Line B to Neutral Units =V (Volts)</p> | SNMP agent |
vVbn<p>Update: 30s</p> |
Peak Current Date [Phase C] | <p>-</p> | SNMP agent |
cdPeakDateTimeL3<p>Update: 30s</p> |
Phase A Load | <p>Host Meter Load Current Phase A Units =A (Amps)</p> | SNMP agent |
lcIa<p>Update: 30s</p> |
Line C to Line A | <p>Host Meter Voltage Line C to Line A Units =V (Volts)</p> | SNMP agent |
vVca<p>Update: 30s</p> |
Frequency | <p>Host Meter Frequency Units =Hz</p> | SNMP agent |
fFrequency<p>Update: 30s</p> |
Voltage Line to Neutral 3 Phase Average | <p>-</p> | SNMP agent |
vVlnAvg<p>Update: 30s</p> |
Peak Current Demand [Phase C] | <p>-</p> | SNMP agent |
cdPeakCurrentDemandL3<p>Update: 30s</p> |
Line C to Neutral | <p>Host Meter Voltage Line C to Neutral Units =V (Volts)</p> | SNMP agent |
vVcn<p>Update: 30s</p> |
Phase C Load | <p>Host Meter Load Current Phase C Units =A (Amps)</p> | SNMP agent |
lcIc<p>Update: 30s</p> |
Line B to Line C | <p>Host Meter Voltage Line B to Line C Units =V (Volts)</p> | SNMP agent |
vVbc<p>Update: 30s</p> |
Phase B Load | <p>Host Meter Load Current Phase B Units =A (Amps)</p> | SNMP agent |
lcIb<p>Update: 30s</p> |
3 Phase Load Average | <p>Host Meter Load Current 3 Phase Average Units =A (Amps)</p> | SNMP agent |
lcIAvg<p>Update: 30s</p> |
Apparent Energy | <p>-</p> | SNMP agent |
eApparentEnergy<p>Update: 30s</p> |
Firmware Version | <p>Host Meter Firmware Version</p> | SNMP agent |
midFirmwareVersion<p>Update: 3600</p> |
Line A to Neutral | <p>Host Meter Voltage Line A to Neutral Units =V (Volts)</p> | SNMP agent |
vVan<p>Update: 30s</p> |
Real power | <p>Host Meter Real Power Units =kW</p> | SNMP agent |
pReal<p>Update: 30s</p> |
Device Name | <p>Host Meter Label plus Nameplate</p> | SNMP agent |
midDeviceName<p>Update: 3600</p> |
Peak Current Date [Phase B] | <p>-</p> | SNMP agent |
cdPeakDateTimeL2<p>Update: 30s</p> |
Peak Current Date [Phase A] | <p>Host Meter Peak Current Demand Date and Time</p> | SNMP agent |
cdPeakDateTimeL1<p>Update: 30s</p> |
There are no triggers in this template.
petroska
There are no macros links in this template.
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Present Current Demand [Phase B] | <p>-</p> | SNMP agent |
cdPresentCurrentDemandL2<p>Update: 30s</p> |
Present Current Demand [Phase A] | <p>Host Meter Present Demand Current Units =A (Amps)</p> | SNMP agent |
cdPresentCurrentDemandL1<p>Update: 30s</p> |
Peak Current Demand [Phase B] | <p>-</p> | SNMP agent |
cdPeakCurrentDemandL2<p>Update: 30s</p> |
Wiring Type | <p>Single Phase Line to Neutral 2 Wire 1CT 1PT is ‘10’ Single Phase Line to Line 2 Wire 1CT 1PT is ‘11’ Single Phase 3-Wire 3 wire 2CT 2PT is ‘12’ Three Phase 3 Wire 2CT 2PT is ‘30’ Three Phase 3 Wire 3CT 2PT is ‘31’ Three Phase 3 Wire 1CT 2PT is ‘32’ Three Phase 4 Wire 3CT 3PT is ‘40’ Three Phase 4 Wire 3CT 2PT is ‘42’ Three Phase 4 Wire 1CT 3PT is ‘44’</p> | SNMP agent |
swtWiringType<p>Update: 3600</p> |
Line A to Line B | <p>Host Meter Voltage Line A to Line B Units =V (Volts)</p> | SNMP agent |
vVab<p>Update: 30s</p> |
Reactive power | <p>Host Meter Reactive Power Units =kVAR</p> | SNMP agent |
pReactive<p>Update: 30s</p> |
Peak Current Demand [Phase A] | <p>Host Meter Peak Current Demand Units =A (Amps)</p> | SNMP agent |
cdPeakCurrentDemandL1<p>Update: 30s</p> |
Apparent power | <p>Host Meter Apparent Power Units =kVA</p> | SNMP agent |
pApparent<p>Update: 30s</p> |
Present Current Demand [Phase C] | <p>-</p> | SNMP agent |
cdPresentCurrentDemandL3<p>Update: 30s</p> |
Reactive Energy | <p>Host Meter Reactive Energy Units =kVARh</p> | SNMP agent |
eReactiveEnergy<p>Update: 30s</p> |
Real Energy | <p>Host Meter Real Energy Units =kWh</p> | SNMP agent |
eRealEnergy<p>Update: 30s</p> |
Power factor description | <p>Describes the current power factor Lead/Lag for IEEE mode Cap/Ind for IEC mode</p> | SNMP agent |
pfPowerFactorDescription<p>Update: 3600</p> |
Model Number | <p>Host Meter Model Number</p> | SNMP agent |
midModelNumber<p>Update: 3600</p> |
Power factor | <p>Host Meter 3 Phase Total Power Factor</p> | SNMP agent |
pfPowerFactorTotal<p>Update: 30s</p> |
Line to Line Average Voltage | <p>Host Meter Voltage Line to Line Average Voltage Units =V (Volts)</p> | SNMP agent |
vVllAvg<p>Update: 30s</p> |
Serial number | <p>Host meter 32 bit Serial Number</p> | SNMP agent |
midSerialNumber<p>Update: 3600</p> |
Line B to Neutral | <p>Host Meter Voltage Line B to Neutral Units =V (Volts)</p> | SNMP agent |
vVbn<p>Update: 30s</p> |
Peak Current Date [Phase C] | <p>-</p> | SNMP agent |
cdPeakDateTimeL3<p>Update: 30s</p> |
Phase A Load | <p>Host Meter Load Current Phase A Units =A (Amps)</p> | SNMP agent |
lcIa<p>Update: 30s</p> |
Line C to Line A | <p>Host Meter Voltage Line C to Line A Units =V (Volts)</p> | SNMP agent |
vVca<p>Update: 30s</p> |
Frequency | <p>Host Meter Frequency Units =Hz</p> | SNMP agent |
fFrequency<p>Update: 30s</p> |
Voltage Line to Neutral 3 Phase Average | <p>-</p> | SNMP agent |
vVlnAvg<p>Update: 30s</p> |
Peak Current Demand [Phase C] | <p>-</p> | SNMP agent |
cdPeakCurrentDemandL3<p>Update: 30s</p> |
Line C to Neutral | <p>Host Meter Voltage Line C to Neutral Units =V (Volts)</p> | SNMP agent |
vVcn<p>Update: 30s</p> |
Phase C Load | <p>Host Meter Load Current Phase C Units =A (Amps)</p> | SNMP agent |
lcIc<p>Update: 30s</p> |
Line B to Line C | <p>Host Meter Voltage Line B to Line C Units =V (Volts)</p> | SNMP agent |
vVbc<p>Update: 30s</p> |
Phase B Load | <p>Host Meter Load Current Phase B Units =A (Amps)</p> | SNMP agent |
lcIb<p>Update: 30s</p> |
3 Phase Load Average | <p>Host Meter Load Current 3 Phase Average Units =A (Amps)</p> | SNMP agent |
lcIAvg<p>Update: 30s</p> |
Apparent Energy | <p>-</p> | SNMP agent |
eApparentEnergy<p>Update: 30s</p> |
Firmware Version | <p>Host Meter Firmware Version</p> | SNMP agent |
midFirmwareVersion<p>Update: 3600</p> |
Line A to Neutral | <p>Host Meter Voltage Line A to Neutral Units =V (Volts)</p> | SNMP agent |
vVan<p>Update: 30s</p> |
Real power | <p>Host Meter Real Power Units =kW</p> | SNMP agent |
pReal<p>Update: 30s</p> |
Device Name | <p>Host Meter Label plus Nameplate</p> | SNMP agent |
midDeviceName<p>Update: 3600</p> |
Peak Current Date [Phase B] | <p>-</p> | SNMP agent |
cdPeakDateTimeL2<p>Update: 30s</p> |
Peak Current Date [Phase A] | <p>Host Meter Peak Current Demand Date and Time</p> | SNMP agent |
cdPeakDateTimeL1<p>Update: 30s</p> |
There are no triggers in this template.