Available versions




SNMP APC NetBotz Rack Monitor 200

Overview

LLD of Sensors (Only Temperature and humidity)

Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature

Graph Prototypes for Temperature and Humidity.

Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert.

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
Internal APC Sensor <p>-</p> SNMP agent apc.enviro.sensor<p>Update: 30</p>

Items collected

Name Description Type Key and additional info
{#SNMPVALUE} Sensor Humidity <p>-</p> SNMP agent apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p>
{#SNMPVALUE} Sensor Temperature <p>-</p> SNMP agent apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p>

Triggers

Name Description Expression Priority
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>55</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>=60</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<45</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<=40</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=15</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=19</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=22</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=24</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=30</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>55</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>=60</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<45</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<=40</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=15</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=19</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=22</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=24</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C (LLD) <p>-</p> <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=30</p><p>Recovery expression: </p> disaster

SNMP APC NetBotz Rack Monitor 200

Overview

LLD of Sensors (Only Temperature and humidity)

Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature

Graph Prototypes for Temperature and Humidity.

Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert.

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
Internal APC Sensor <p>-</p> SNMP agent apc.enviro.sensor<p>Update: 30</p>

Items collected

Name Description Type Key and additional info
{#SNMPVALUE} Sensor Humidity <p>-</p> SNMP agent apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p>
{#SNMPVALUE} Sensor Temperature <p>-</p> SNMP agent apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p>

Triggers

Name Description Expression Priority
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> disaster

SNMP APC NetBotz Rack Monitor 200

Overview

LLD of Sensors (Only Temperature and humidity)

Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature

Graph Prototypes for Temperature and Humidity.

Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert.

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
Internal APC Sensor <p>-</p> SNMP agent apc.enviro.sensor<p>Update: 30</p>

Items collected

Name Description Type Key and additional info
{#SNMPVALUE} Sensor Humidity <p>-</p> SNMP agent apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p>
{#SNMPVALUE} Sensor Temperature <p>-</p> SNMP agent apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p>

Triggers

Name Description Expression Priority
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> disaster
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> warning
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> high
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C (LLD) <p>-</p> <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> disaster