LLD of Sensors (Only Temperature and humidity)
Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature
Graph Prototypes for Temperature and Humidity.
Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert.
There are no macros links in this template.
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Internal APC Sensor | <p>-</p> | SNMP agent |
apc.enviro.sensor<p>Update: 30</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#SNMPVALUE} Sensor Humidity | <p>-</p> | SNMP agent |
apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p> |
{#SNMPVALUE} Sensor Temperature | <p>-</p> | SNMP agent |
apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>55</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>=60</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<45</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<=40</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=15</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=19</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=22</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=24</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=30</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>55</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}>=60</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<45</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”].last()}<=40</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=15</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}<=19</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=22</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=24</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C (LLD) | <p>-</p> | <p>Expression: {SNMP APC NetBotz Rack Monitor 200:apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”].last()}>=30</p><p>Recovery expression: </p> | disaster |
LLD of Sensors (Only Temperature and humidity)
Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature
Graph Prototypes for Temperature and Humidity.
Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert.
There are no macros links in this template.
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Internal APC Sensor | <p>-</p> | SNMP agent |
apc.enviro.sensor<p>Update: 30</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#SNMPVALUE} Sensor Humidity | <p>-</p> | SNMP agent |
apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p> |
{#SNMPVALUE} Sensor Temperature | <p>-</p> | SNMP agent |
apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> | disaster |
LLD of Sensors (Only Temperature and humidity)
Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature
Graph Prototypes for Temperature and Humidity.
Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert.
There are no macros links in this template.
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Internal APC Sensor | <p>-</p> | SNMP agent |
apc.enviro.sensor<p>Update: 30</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#SNMPVALUE} Sensor Humidity | <p>-</p> | SNMP agent |
apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p> |
{#SNMPVALUE} Sensor Temperature | <p>-</p> | SNMP agent |
apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”]<p>Update: 30</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>55</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])>=60</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<45</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH% (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.[”{#SNMPINDEX}”])<=40</p><p>Recovery expression: </p> | disaster |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=15</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])<=19</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=22</p><p>Recovery expression: </p> | warning |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=24</p><p>Recovery expression: </p> | high |
{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C (LLD) | <p>-</p> | <p>Expression: last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.[”{#SNMPINDEX}”])>=30</p><p>Recovery expression: </p> | disaster |