Full clone of Template UPS - diogont (thanks Diogo Teixeira). Above you view the main changes for this template:
For the metrics. We included the measurements 2 and 3:
Pay attention
For triggers in my case 38 has disabled. we added this SNMP Check connect what check if the UPS have snmp connectivity. If past ten minute without data
Marcos Sousa
There are no macros links in this template.
Name |
---|
Template Module ICMP Ping |
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
UPS input power 2 | <p>-</p> | SNMP agent |
upsAdvInputPower2<p>Update: 1m</p> |
UPS input current 2 | <p>-</p> | SNMP agent |
upsAdvInputCurrent2<p>Update: 1m</p> |
UPS input power 1 | <p>-</p> | SNMP agent |
upsAdvInputPower1<p>Update: 1m</p> |
UPS battery capacity (%) | <p>-</p> | SNMP agent |
upsAdvBatteryCapacity<p>Update: 1m</p> |
Device Name | <p>-</p> | SNMP agent |
sysName<p>Update: 1m</p> |
UPS output load 2 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad2<p>Update: 1m</p> |
UPS output load 3 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad3<p>Update: 1m</p> |
UPS output voltage 3 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage3<p>Update: 1m</p> |
UPS output current 2 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent2<p>Update: 1m</p> |
UPS input frequency 2 | <p>-</p> | SNMP agent |
upsAdvInputFrequency2<p>Update: 1m</p> |
UPS input voltage 3 | <p>-</p> | SNMP agent |
upsAdvInputVoltage3<p>Update: 1m</p> |
UPS input frequency 1 | <p>-</p> | SNMP agent |
upsAdvInputFrequency1<p>Update: 1m</p> |
UPS input current 3 | <p>-</p> | SNMP agent |
upsAdvInputCurrent3<p>Update: 1m</p> |
Contact | <p>-</p> | SNMP agent |
sysContact<p>Update: 1m</p> |
UPS output power 3 | <p>-</p> | SNMP agent |
upsAdvOutputPower3<p>Update: 1m</p> |
UPS output frequency | <p>-</p> | SNMP agent |
upsAdvOutputFrequency<p>Update: 1m</p> |
UPS Alarm Input Bad | <p>-</p> | SNMP agent |
upsAlarmInputBad<p>Update: 1m</p> |
UPS output current 1 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent1<p>Update: 1m</p> |
Software version (full) | <p>-</p> | SNMP agent |
sysDescr<p>Update: 1m</p> |
UPS input voltage 1 | <p>-</p> | SNMP agent |
upsAdvInputVoltage1<p>Update: 1m</p> |
UPS output current 3 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent3<p>Update: 1m</p> |
UPS input voltage 2 | <p>-</p> | SNMP agent |
upsAdvInputVoltage2<p>Update: 1m</p> |
UPS Alarm Output Overload | <p>-</p> | SNMP agent |
upsAlarmOutputOverload<p>Update: 1m</p> |
UPS output voltage 2 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage2<p>Update: 1m</p> |
UPS output power 1 | <p>-</p> | SNMP agent |
upsAdvOutputPower1<p>Update: 1m</p> |
Device Location | <p>-</p> | SNMP agent |
sysLocation<p>Update: 1m</p> |
UPS run time remaining | <p>-</p> | SNMP agent |
upsAdvRunTimeRemaining<p>Update: 1m</p> |
Uptime | <p>-</p> | SNMP agent |
sysUpTime<p>Update: 1m</p> |
UPS input frequency 3 | <p>-</p> | SNMP agent |
upsAdvInputFrequency3<p>Update: 1m</p> |
UPS battery status | <p>-</p> | SNMP agent |
upsBasicBatteryStatus<p>Update: 1m</p> |
UPS time on battery | <p>-</p> | SNMP agent |
upsBasicBatteryTimeOnBattery<p>Update: 1m</p> |
UPS battery temperature | <p>-</p> | SNMP agent |
upsAdvBatteryTemperature<p>Update: 1m</p> |
UPS output voltage 1 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage1<p>Update: 1m</p> |
UPS output load 1 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad1<p>Update: 1m</p> |
UPS input power 3 | <p>-</p> | SNMP agent |
upsAdvInputPower3<p>Update: 1m</p> |
UPS input current 1 | <p>-</p> | SNMP agent |
upsAdvInputCurrent1<p>Update: 1m</p> |
UPS output power 2 | <p>-</p> | SNMP agent |
upsAdvOutputPower2<p>Update: 1m</p> |
There are no triggers in this template.
Full clone of Template UPS - diogont (thanks Diogo Teixeira). Above you view the main changes for this template:
For the metrics. We included the measurements 2 and 3:
Pay attention
For triggers in my case 38 has disabled. we added this SNMP Check connect what check if the UPS have snmp connectivity. If past ten minute without data
Marcos Sousa
There are no macros links in this template.
Name |
---|
Template Module ICMP Ping |
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Device Name | <p>-</p> | SNMP agent |
sysName<p>Update: 1m</p> |
UPS output voltage 2 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage2<p>Update: 1m</p> |
UPS input power 1 | <p>-</p> | SNMP agent |
upsAdvInputPower1<p>Update: 1m</p> |
UPS input power 2 | <p>-</p> | SNMP agent |
upsAdvInputPower2<p>Update: 1m</p> |
UPS run time remaining | <p>-</p> | SNMP agent |
upsAdvRunTimeRemaining<p>Update: 1m</p> |
UPS output current 3 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent3<p>Update: 1m</p> |
Uptime | <p>-</p> | SNMP agent |
sysUpTime<p>Update: 1m</p> |
UPS input voltage 1 | <p>-</p> | SNMP agent |
upsAdvInputVoltage1<p>Update: 1m</p> |
Contact | <p>-</p> | SNMP agent |
sysContact<p>Update: 1m</p> |
UPS input frequency 1 | <p>-</p> | SNMP agent |
upsAdvInputFrequency1<p>Update: 1m</p> |
UPS output current 2 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent2<p>Update: 1m</p> |
UPS input power 3 | <p>-</p> | SNMP agent |
upsAdvInputPower3<p>Update: 1m</p> |
UPS output voltage 1 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage1<p>Update: 1m</p> |
UPS input voltage 3 | <p>-</p> | SNMP agent |
upsAdvInputVoltage3<p>Update: 1m</p> |
UPS input current 3 | <p>-</p> | SNMP agent |
upsAdvInputCurrent3<p>Update: 1m</p> |
UPS output frequency | <p>-</p> | SNMP agent |
upsAdvOutputFrequency<p>Update: 1m</p> |
UPS output power 2 | <p>-</p> | SNMP agent |
upsAdvOutputPower2<p>Update: 1m</p> |
UPS output load 1 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad1<p>Update: 1m</p> |
UPS Alarm Input Bad | <p>-</p> | SNMP agent |
upsAlarmInputBad<p>Update: 1m</p> |
UPS battery status | <p>-</p> | SNMP agent |
upsBasicBatteryStatus<p>Update: 1m</p> |
UPS input frequency 2 | <p>-</p> | SNMP agent |
upsAdvInputFrequency2<p>Update: 1m</p> |
UPS input current 1 | <p>-</p> | SNMP agent |
upsAdvInputCurrent1<p>Update: 1m</p> |
UPS output load 3 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad3<p>Update: 1m</p> |
UPS battery capacity (%) | <p>-</p> | SNMP agent |
upsAdvBatteryCapacity<p>Update: 1m</p> |
UPS input voltage 2 | <p>-</p> | SNMP agent |
upsAdvInputVoltage2<p>Update: 1m</p> |
UPS output load 2 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad2<p>Update: 1m</p> |
UPS output current 1 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent1<p>Update: 1m</p> |
Software version (full) | <p>-</p> | SNMP agent |
sysDescr<p>Update: 1m</p> |
UPS output power 1 | <p>-</p> | SNMP agent |
upsAdvOutputPower1<p>Update: 1m</p> |
UPS output voltage 3 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage3<p>Update: 1m</p> |
Device Location | <p>-</p> | SNMP agent |
sysLocation<p>Update: 1m</p> |
UPS output power 3 | <p>-</p> | SNMP agent |
upsAdvOutputPower3<p>Update: 1m</p> |
UPS battery temperature | <p>-</p> | SNMP agent |
upsAdvBatteryTemperature<p>Update: 1m</p> |
UPS Alarm Output Overload | <p>-</p> | SNMP agent |
upsAlarmOutputOverload<p>Update: 1m</p> |
UPS time on battery | <p>-</p> | SNMP agent |
upsBasicBatteryTimeOnBattery<p>Update: 1m</p> |
UPS input current 2 | <p>-</p> | SNMP agent |
upsAdvInputCurrent2<p>Update: 1m</p> |
UPS input frequency 3 | <p>-</p> | SNMP agent |
upsAdvInputFrequency3<p>Update: 1m</p> |
There are no triggers in this template.
Full clone of Template UPS - diogont (thanks Diogo Teixeira). Above you view the main changes for this template:
For the metrics. We included the measurements 2 and 3:
Pay attention
For triggers in my case 38 has disabled. we added this SNMP Check connect what check if the UPS have snmp connectivity. If past ten minute without data
Marcos Sousa
There are no macros links in this template.
Name |
---|
Template Module ICMP Ping |
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Device Name | <p>-</p> | SNMP agent |
sysName<p>Update: 1m</p> |
UPS output voltage 2 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage2<p>Update: 1m</p> |
UPS input power 1 | <p>-</p> | SNMP agent |
upsAdvInputPower1<p>Update: 1m</p> |
UPS input power 2 | <p>-</p> | SNMP agent |
upsAdvInputPower2<p>Update: 1m</p> |
UPS run time remaining | <p>-</p> | SNMP agent |
upsAdvRunTimeRemaining<p>Update: 1m</p> |
UPS output current 3 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent3<p>Update: 1m</p> |
Uptime | <p>-</p> | SNMP agent |
sysUpTime<p>Update: 1m</p> |
UPS input voltage 1 | <p>-</p> | SNMP agent |
upsAdvInputVoltage1<p>Update: 1m</p> |
Contact | <p>-</p> | SNMP agent |
sysContact<p>Update: 1m</p> |
UPS input frequency 1 | <p>-</p> | SNMP agent |
upsAdvInputFrequency1<p>Update: 1m</p> |
UPS output current 2 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent2<p>Update: 1m</p> |
UPS input power 3 | <p>-</p> | SNMP agent |
upsAdvInputPower3<p>Update: 1m</p> |
UPS output voltage 1 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage1<p>Update: 1m</p> |
UPS input voltage 3 | <p>-</p> | SNMP agent |
upsAdvInputVoltage3<p>Update: 1m</p> |
UPS input current 3 | <p>-</p> | SNMP agent |
upsAdvInputCurrent3<p>Update: 1m</p> |
UPS output frequency | <p>-</p> | SNMP agent |
upsAdvOutputFrequency<p>Update: 1m</p> |
UPS output power 2 | <p>-</p> | SNMP agent |
upsAdvOutputPower2<p>Update: 1m</p> |
UPS output load 1 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad1<p>Update: 1m</p> |
UPS Alarm Input Bad | <p>-</p> | SNMP agent |
upsAlarmInputBad<p>Update: 1m</p> |
UPS battery status | <p>-</p> | SNMP agent |
upsBasicBatteryStatus<p>Update: 1m</p> |
UPS input frequency 2 | <p>-</p> | SNMP agent |
upsAdvInputFrequency2<p>Update: 1m</p> |
UPS input current 1 | <p>-</p> | SNMP agent |
upsAdvInputCurrent1<p>Update: 1m</p> |
UPS output load 3 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad3<p>Update: 1m</p> |
UPS battery capacity (%) | <p>-</p> | SNMP agent |
upsAdvBatteryCapacity<p>Update: 1m</p> |
UPS input voltage 2 | <p>-</p> | SNMP agent |
upsAdvInputVoltage2<p>Update: 1m</p> |
UPS output load 2 (%) | <p>-</p> | SNMP agent |
upsAdvOutputLoad2<p>Update: 1m</p> |
UPS output current 1 | <p>-</p> | SNMP agent |
upsAdvOutputCurrent1<p>Update: 1m</p> |
Software version (full) | <p>-</p> | SNMP agent |
sysDescr<p>Update: 1m</p> |
UPS output power 1 | <p>-</p> | SNMP agent |
upsAdvOutputPower1<p>Update: 1m</p> |
UPS output voltage 3 | <p>-</p> | SNMP agent |
upsAdvOutputVoltage3<p>Update: 1m</p> |
Device Location | <p>-</p> | SNMP agent |
sysLocation<p>Update: 1m</p> |
UPS output power 3 | <p>-</p> | SNMP agent |
upsAdvOutputPower3<p>Update: 1m</p> |
UPS battery temperature | <p>-</p> | SNMP agent |
upsAdvBatteryTemperature<p>Update: 1m</p> |
UPS Alarm Output Overload | <p>-</p> | SNMP agent |
upsAlarmOutputOverload<p>Update: 1m</p> |
UPS time on battery | <p>-</p> | SNMP agent |
upsBasicBatteryTimeOnBattery<p>Update: 1m</p> |
UPS input current 2 | <p>-</p> | SNMP agent |
upsAdvInputCurrent2<p>Update: 1m</p> |
UPS input frequency 3 | <p>-</p> | SNMP agent |
upsAdvInputFrequency3<p>Update: 1m</p> |
There are no triggers in this template.