Available versions




SOCOMEC UPS

Overview

This templase include some info and trigger such as:

You just edit the SNMP_COMMUNITY value into the template

Author

diablofight89

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> afLpogHP16EW Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Firmware Version <p>-</p> SNMP agent upsfirmware.0<p>Update: 1d</p>
Alarm - UPS OnBattery Power <p>“The UPS is drawing power from the batteries. (A019)”</p> SNMP agent upsAlarmOnBattery<p>Update: 1m</p>
Output Load <p>“Output global Load Rate.”</p> SNMP agent upsOutputLoadRate.0<p>Update: 1m</p>
Battery Status <p>“The present battery status”</p> SNMP agent upsBatteryStatus.0<p>Update: 1m</p>
Ambient Temperature <p>“The ambient temperature inside the UPS in 0.1 degree”</p> SNMP agent upsAmbientTemperature.0<p>Update: 1m</p>
Battery Time Remaining <p>“An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power”</p> SNMP agent upsEstimatedMinutesRemaining.0<p>Update: 1m</p>
Alarm - UPS Overload <p>“The output load exceeds the UPS output capacity. (A001)”</p> SNMP agent upsAlarmOverload.0<p>Update: 1m</p>
Battery Percent <p>“An estimate of the battery charge remaining expressed as a percent of full charge.”</p> SNMP agent upsEstimatedChargeRemaining.0<p>Update: 1m</p>
Ping check <p>-</p> Simple check icmpping<p>Update: 30s</p>
Alarm - UPS OnBypass <p>“Load supplied by automatic bypass. Load not protected.”</p> SNMP agent upsAlarmOnBypass.0<p>Update: 1m</p>
Serial Number <p>-</p> SNMP agent upsIdentSerialNumber.0<p>Update: 1d</p>
Alarm - UPS LowBattery <p>“The remaining battery run-time is less than or equal to battery low threshold. (A018)”</p> SNMP agent upsAlarmLowBattery.0<p>Update: 1m</p>
Output Frequency <p>“The current output frequency of the UPS system in 0.1 of HZ.”</p> SNMP agent upsOutputFrequency.0<p>Update: 1m</p>
Alarm Present Quantity <p>“The present number of active alarm conditions.”</p> SNMP agent upsAlarmsPresent.0<p>Update: 1m</p>
Alarm - Battery Temperature <p>“Battery Temperature Alarm. (A020)”</p> SNMP agent upsAlarmBatteryTemperature.0<p>Update: 1m</p>
Model <p>-</p> SNMP agent upsIdentModel.0<p>Update: 1d</p>
Input Frequency <p>“The current input frequency to the UPS system in 0.1 HZ.”</p> SNMP agent upsInputFrequency.0<p>Update: 1m</p>
Output Status <p>“The present source of output power.”</p> SNMP agent upsOutputSource.0<p>Update: 1m</p>
Alarm - Fan Fault <p>“Fans failure. (A054)”</p> SNMP agent upsAlarmFansFailure.0<p>Update: 1m</p>
Battery Voltage <p>“The magnitude of the present battery voltage in 0.1 Volt DC.”</p> SNMP agent upsBatteryVoltage.0<p>Update: 1m</p>

Triggers

There are no triggers in this template.

SOCOMEC UPS

Overview

This templase include some info and trigger such as:

You just edit the SNMP_COMMUNITY value into the template

Author

diablofight89

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> afLpogHP16EW Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Battery Status <p>“The present battery status”</p> SNMP agent upsBatteryStatus.0<p>Update: 1m</p>
Output Frequency <p>“The current output frequency of the UPS system in 0.1 of HZ.”</p> SNMP agent upsOutputFrequency.0<p>Update: 1m</p>
Ambient Temperature <p>“The ambient temperature inside the UPS in 0.1 degree”</p> SNMP agent upsAmbientTemperature.0<p>Update: 1m</p>
Alarm - UPS OnBattery Power <p>“The UPS is drawing power from the batteries. (A019)”</p> SNMP agent upsAlarmOnBattery<p>Update: 1m</p>
Ping check <p>-</p> Simple check icmpping<p>Update: 30s</p>
Alarm - UPS Overload <p>“The output load exceeds the UPS output capacity. (A001)”</p> SNMP agent upsAlarmOverload.0<p>Update: 1m</p>
Battery Time Remaining <p>“An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power”</p> SNMP agent upsEstimatedMinutesRemaining.0<p>Update: 1m</p>
Output Load <p>“Output global Load Rate.”</p> SNMP agent upsOutputLoadRate.0<p>Update: 1m</p>
Alarm - Battery Temperature <p>“Battery Temperature Alarm. (A020)”</p> SNMP agent upsAlarmBatteryTemperature.0<p>Update: 1m</p>
Alarm - Fan Fault <p>“Fans failure. (A054)”</p> SNMP agent upsAlarmFansFailure.0<p>Update: 1m</p>
Input Frequency <p>“The current input frequency to the UPS system in 0.1 HZ.”</p> SNMP agent upsInputFrequency.0<p>Update: 1m</p>
Battery Voltage <p>“The magnitude of the present battery voltage in 0.1 Volt DC.”</p> SNMP agent upsBatteryVoltage.0<p>Update: 1m</p>
Alarm - UPS OnBypass <p>“Load supplied by automatic bypass. Load not protected.”</p> SNMP agent upsAlarmOnBypass.0<p>Update: 1m</p>
Model <p>-</p> SNMP agent upsIdentModel.0<p>Update: 1d</p>
Battery Percent <p>“An estimate of the battery charge remaining expressed as a percent of full charge.”</p> SNMP agent upsEstimatedChargeRemaining.0<p>Update: 1m</p>
Serial Number <p>-</p> SNMP agent upsIdentSerialNumber.0<p>Update: 1d</p>
Firmware Version <p>-</p> SNMP agent upsfirmware.0<p>Update: 1d</p>
Output Status <p>“The present source of output power.”</p> SNMP agent upsOutputSource.0<p>Update: 1m</p>
Alarm - UPS LowBattery <p>“The remaining battery run-time is less than or equal to battery low threshold. (A018)”</p> SNMP agent upsAlarmLowBattery.0<p>Update: 1m</p>
Alarm Present Quantity <p>“The present number of active alarm conditions.”</p> SNMP agent upsAlarmsPresent.0<p>Update: 1m</p>

Triggers

There are no triggers in this template.

SOCOMEC UPS

Overview

This templase include some info and trigger such as:

You just edit the SNMP_COMMUNITY value into the template

Author

diablofight89

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> afLpogHP16EW Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Battery Status <p>“The present battery status”</p> SNMP agent upsBatteryStatus.0<p>Update: 1m</p>
Output Frequency <p>“The current output frequency of the UPS system in 0.1 of HZ.”</p> SNMP agent upsOutputFrequency.0<p>Update: 1m</p>
Ambient Temperature <p>“The ambient temperature inside the UPS in 0.1 degree”</p> SNMP agent upsAmbientTemperature.0<p>Update: 1m</p>
Alarm - UPS OnBattery Power <p>“The UPS is drawing power from the batteries. (A019)”</p> SNMP agent upsAlarmOnBattery<p>Update: 1m</p>
Ping check <p>-</p> Simple check icmpping<p>Update: 30s</p>
Alarm - UPS Overload <p>“The output load exceeds the UPS output capacity. (A001)”</p> SNMP agent upsAlarmOverload.0<p>Update: 1m</p>
Battery Time Remaining <p>“An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power”</p> SNMP agent upsEstimatedMinutesRemaining.0<p>Update: 1m</p>
Output Load <p>“Output global Load Rate.”</p> SNMP agent upsOutputLoadRate.0<p>Update: 1m</p>
Alarm - Battery Temperature <p>“Battery Temperature Alarm. (A020)”</p> SNMP agent upsAlarmBatteryTemperature.0<p>Update: 1m</p>
Alarm - Fan Fault <p>“Fans failure. (A054)”</p> SNMP agent upsAlarmFansFailure.0<p>Update: 1m</p>
Input Frequency <p>“The current input frequency to the UPS system in 0.1 HZ.”</p> SNMP agent upsInputFrequency.0<p>Update: 1m</p>
Battery Voltage <p>“The magnitude of the present battery voltage in 0.1 Volt DC.”</p> SNMP agent upsBatteryVoltage.0<p>Update: 1m</p>
Alarm - UPS OnBypass <p>“Load supplied by automatic bypass. Load not protected.”</p> SNMP agent upsAlarmOnBypass.0<p>Update: 1m</p>
Model <p>-</p> SNMP agent upsIdentModel.0<p>Update: 1d</p>
Battery Percent <p>“An estimate of the battery charge remaining expressed as a percent of full charge.”</p> SNMP agent upsEstimatedChargeRemaining.0<p>Update: 1m</p>
Serial Number <p>-</p> SNMP agent upsIdentSerialNumber.0<p>Update: 1d</p>
Firmware Version <p>-</p> SNMP agent upsfirmware.0<p>Update: 1d</p>
Output Status <p>“The present source of output power.”</p> SNMP agent upsOutputSource.0<p>Update: 1m</p>
Alarm - UPS LowBattery <p>“The remaining battery run-time is less than or equal to battery low threshold. (A018)”</p> SNMP agent upsAlarmLowBattery.0<p>Update: 1m</p>
Alarm Present Quantity <p>“The present number of active alarm conditions.”</p> SNMP agent upsAlarmsPresent.0<p>Update: 1m</p>

Triggers

There are no triggers in this template.