This templase include some info and trigger such as:
Battery
Temperature
Output
Alarms
You just edit the SNMP_COMMUNITY value into the template
diablofight89
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | afLpogHP16EW |
Text macro |
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Firmware Version | <p>-</p> | SNMP agent |
upsfirmware.0<p>Update: 1d</p> |
Alarm - UPS OnBattery Power | <p>“The UPS is drawing power from the batteries. (A019)”</p> | SNMP agent |
upsAlarmOnBattery<p>Update: 1m</p> |
Output Load | <p>“Output global Load Rate.”</p> | SNMP agent |
upsOutputLoadRate.0<p>Update: 1m</p> |
Battery Status | <p>“The present battery status”</p> | SNMP agent |
upsBatteryStatus.0<p>Update: 1m</p> |
Ambient Temperature | <p>“The ambient temperature inside the UPS in 0.1 degree”</p> | SNMP agent |
upsAmbientTemperature.0<p>Update: 1m</p> |
Battery Time Remaining | <p>“An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power”</p> | SNMP agent |
upsEstimatedMinutesRemaining.0<p>Update: 1m</p> |
Alarm - UPS Overload | <p>“The output load exceeds the UPS output capacity. (A001)”</p> | SNMP agent |
upsAlarmOverload.0<p>Update: 1m</p> |
Battery Percent | <p>“An estimate of the battery charge remaining expressed as a percent of full charge.”</p> | SNMP agent |
upsEstimatedChargeRemaining.0<p>Update: 1m</p> |
Ping check | <p>-</p> | Simple check |
icmpping<p>Update: 30s</p> |
Alarm - UPS OnBypass | <p>“Load supplied by automatic bypass. Load not protected.”</p> | SNMP agent |
upsAlarmOnBypass.0<p>Update: 1m</p> |
Serial Number | <p>-</p> | SNMP agent |
upsIdentSerialNumber.0<p>Update: 1d</p> |
Alarm - UPS LowBattery | <p>“The remaining battery run-time is less than or equal to battery low threshold. (A018)”</p> | SNMP agent |
upsAlarmLowBattery.0<p>Update: 1m</p> |
Output Frequency | <p>“The current output frequency of the UPS system in 0.1 of HZ.”</p> | SNMP agent |
upsOutputFrequency.0<p>Update: 1m</p> |
Alarm Present Quantity | <p>“The present number of active alarm conditions.”</p> | SNMP agent |
upsAlarmsPresent.0<p>Update: 1m</p> |
Alarm - Battery Temperature | <p>“Battery Temperature Alarm. (A020)”</p> | SNMP agent |
upsAlarmBatteryTemperature.0<p>Update: 1m</p> |
Model | <p>-</p> | SNMP agent |
upsIdentModel.0<p>Update: 1d</p> |
Input Frequency | <p>“The current input frequency to the UPS system in 0.1 HZ.”</p> | SNMP agent |
upsInputFrequency.0<p>Update: 1m</p> |
Output Status | <p>“The present source of output power.”</p> | SNMP agent |
upsOutputSource.0<p>Update: 1m</p> |
Alarm - Fan Fault | <p>“Fans failure. (A054)”</p> | SNMP agent |
upsAlarmFansFailure.0<p>Update: 1m</p> |
Battery Voltage | <p>“The magnitude of the present battery voltage in 0.1 Volt DC.”</p> | SNMP agent |
upsBatteryVoltage.0<p>Update: 1m</p> |
There are no triggers in this template.
This templase include some info and trigger such as:
Battery
Temperature
Output
Alarms
You just edit the SNMP_COMMUNITY value into the template
diablofight89
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | afLpogHP16EW |
Text macro |
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Battery Status | <p>“The present battery status”</p> | SNMP agent |
upsBatteryStatus.0<p>Update: 1m</p> |
Output Frequency | <p>“The current output frequency of the UPS system in 0.1 of HZ.”</p> | SNMP agent |
upsOutputFrequency.0<p>Update: 1m</p> |
Ambient Temperature | <p>“The ambient temperature inside the UPS in 0.1 degree”</p> | SNMP agent |
upsAmbientTemperature.0<p>Update: 1m</p> |
Alarm - UPS OnBattery Power | <p>“The UPS is drawing power from the batteries. (A019)”</p> | SNMP agent |
upsAlarmOnBattery<p>Update: 1m</p> |
Ping check | <p>-</p> | Simple check |
icmpping<p>Update: 30s</p> |
Alarm - UPS Overload | <p>“The output load exceeds the UPS output capacity. (A001)”</p> | SNMP agent |
upsAlarmOverload.0<p>Update: 1m</p> |
Battery Time Remaining | <p>“An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power”</p> | SNMP agent |
upsEstimatedMinutesRemaining.0<p>Update: 1m</p> |
Output Load | <p>“Output global Load Rate.”</p> | SNMP agent |
upsOutputLoadRate.0<p>Update: 1m</p> |
Alarm - Battery Temperature | <p>“Battery Temperature Alarm. (A020)”</p> | SNMP agent |
upsAlarmBatteryTemperature.0<p>Update: 1m</p> |
Alarm - Fan Fault | <p>“Fans failure. (A054)”</p> | SNMP agent |
upsAlarmFansFailure.0<p>Update: 1m</p> |
Input Frequency | <p>“The current input frequency to the UPS system in 0.1 HZ.”</p> | SNMP agent |
upsInputFrequency.0<p>Update: 1m</p> |
Battery Voltage | <p>“The magnitude of the present battery voltage in 0.1 Volt DC.”</p> | SNMP agent |
upsBatteryVoltage.0<p>Update: 1m</p> |
Alarm - UPS OnBypass | <p>“Load supplied by automatic bypass. Load not protected.”</p> | SNMP agent |
upsAlarmOnBypass.0<p>Update: 1m</p> |
Model | <p>-</p> | SNMP agent |
upsIdentModel.0<p>Update: 1d</p> |
Battery Percent | <p>“An estimate of the battery charge remaining expressed as a percent of full charge.”</p> | SNMP agent |
upsEstimatedChargeRemaining.0<p>Update: 1m</p> |
Serial Number | <p>-</p> | SNMP agent |
upsIdentSerialNumber.0<p>Update: 1d</p> |
Firmware Version | <p>-</p> | SNMP agent |
upsfirmware.0<p>Update: 1d</p> |
Output Status | <p>“The present source of output power.”</p> | SNMP agent |
upsOutputSource.0<p>Update: 1m</p> |
Alarm - UPS LowBattery | <p>“The remaining battery run-time is less than or equal to battery low threshold. (A018)”</p> | SNMP agent |
upsAlarmLowBattery.0<p>Update: 1m</p> |
Alarm Present Quantity | <p>“The present number of active alarm conditions.”</p> | SNMP agent |
upsAlarmsPresent.0<p>Update: 1m</p> |
There are no triggers in this template.
This templase include some info and trigger such as:
Battery
Temperature
Output
Alarms
You just edit the SNMP_COMMUNITY value into the template
diablofight89
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | afLpogHP16EW |
Text macro |
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Battery Status | <p>“The present battery status”</p> | SNMP agent |
upsBatteryStatus.0<p>Update: 1m</p> |
Output Frequency | <p>“The current output frequency of the UPS system in 0.1 of HZ.”</p> | SNMP agent |
upsOutputFrequency.0<p>Update: 1m</p> |
Ambient Temperature | <p>“The ambient temperature inside the UPS in 0.1 degree”</p> | SNMP agent |
upsAmbientTemperature.0<p>Update: 1m</p> |
Alarm - UPS OnBattery Power | <p>“The UPS is drawing power from the batteries. (A019)”</p> | SNMP agent |
upsAlarmOnBattery<p>Update: 1m</p> |
Ping check | <p>-</p> | Simple check |
icmpping<p>Update: 30s</p> |
Alarm - UPS Overload | <p>“The output load exceeds the UPS output capacity. (A001)”</p> | SNMP agent |
upsAlarmOverload.0<p>Update: 1m</p> |
Battery Time Remaining | <p>“An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power”</p> | SNMP agent |
upsEstimatedMinutesRemaining.0<p>Update: 1m</p> |
Output Load | <p>“Output global Load Rate.”</p> | SNMP agent |
upsOutputLoadRate.0<p>Update: 1m</p> |
Alarm - Battery Temperature | <p>“Battery Temperature Alarm. (A020)”</p> | SNMP agent |
upsAlarmBatteryTemperature.0<p>Update: 1m</p> |
Alarm - Fan Fault | <p>“Fans failure. (A054)”</p> | SNMP agent |
upsAlarmFansFailure.0<p>Update: 1m</p> |
Input Frequency | <p>“The current input frequency to the UPS system in 0.1 HZ.”</p> | SNMP agent |
upsInputFrequency.0<p>Update: 1m</p> |
Battery Voltage | <p>“The magnitude of the present battery voltage in 0.1 Volt DC.”</p> | SNMP agent |
upsBatteryVoltage.0<p>Update: 1m</p> |
Alarm - UPS OnBypass | <p>“Load supplied by automatic bypass. Load not protected.”</p> | SNMP agent |
upsAlarmOnBypass.0<p>Update: 1m</p> |
Model | <p>-</p> | SNMP agent |
upsIdentModel.0<p>Update: 1d</p> |
Battery Percent | <p>“An estimate of the battery charge remaining expressed as a percent of full charge.”</p> | SNMP agent |
upsEstimatedChargeRemaining.0<p>Update: 1m</p> |
Serial Number | <p>-</p> | SNMP agent |
upsIdentSerialNumber.0<p>Update: 1d</p> |
Firmware Version | <p>-</p> | SNMP agent |
upsfirmware.0<p>Update: 1d</p> |
Output Status | <p>“The present source of output power.”</p> | SNMP agent |
upsOutputSource.0<p>Update: 1m</p> |
Alarm - UPS LowBattery | <p>“The remaining battery run-time is less than or equal to battery low threshold. (A018)”</p> | SNMP agent |
upsAlarmLowBattery.0<p>Update: 1m</p> |
Alarm Present Quantity | <p>“The present number of active alarm conditions.”</p> | SNMP agent |
upsAlarmsPresent.0<p>Update: 1m</p> |
There are no triggers in this template.