Available versions




HW UPS Legrand CS141

Overview

Template for monitoring UPS Legrand CS 141 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/

The content of template:

5 Applications: General, Health, Input, Output, Battery

18 Items:

Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage

Alarms present on {HOST.NAME}, Bypass Current, Bypass Power

Input line bads, Output Power, Output load in percent

Seconds on battery, Output Voltage

Estimated charge remaining, Battery voltage

Battery temperature, Device Version

Device Name, Device Model

13 Triggers and 4 Graphs

The template use SNMP agent v2. Assure that you set the community in template macros.

Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values

1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted

Send me what template you need, or if this template helped you, you can buy me one coffee :)

Upgraded template from Tudor Ticau

Author

Dusan Priechodsky

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
UPS Bypass Phases <p>-</p> SNMP agent upsBypassCurrent<p>Update: 1h</p>
UPS Output Phses <p>-</p> SNMP agent upsOutputPower<p>Update: 1h</p>
UPS Input Phases <p>-</p> SNMP agent upsInputFrequency<p>Update: 1h</p>

Items collected

Name Description Type Key and additional info
Seconds on battery <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> SNMP agent upsSecondsOnBattery<p>Update: 30</p>
Device Vendor <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentManufacturer<p>Update: 600</p>
Alarms present on {HOST.NAME} <p>The present number of active alarm conditions.</p> SNMP agent upsAlarmsPresent<p>Update: 30</p>
Input line bads <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> SNMP agent upsInputLineBads<p>Update: 30</p>
Battery Status <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> SNMP agent upsBatteryStatus<p>Update: 30</p>
Device Uptime <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentUptime<p>Update: 1m</p>
Battery voltage <p>The magnitude of the present battery voltage.</p> SNMP agent upsBatteryVoltage<p>Update: 60</p>
Device Name <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentName<p>Update: 600</p>
Estimated minutes remaining if no power <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> SNMP agent upsEstimatedMinutesRemaining<p>Update: 30</p>
Device Model <p>The UPS Model designation.</p> SNMP agent upsIdentModel<p>Update: 86400</p>
Device Location <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentLocation<p>Update: 600</p>
Battery temperature <p>The ambient temperature at or near the UPS Battery casing.</p> SNMP agent upsBatteryTemperature<p>Update: 60</p>
Estimated charge remaining <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> SNMP agent upsEstimatedChargeRemaining<p>Update: 60</p>
Device Version <p>The UPS agent software version.</p> SNMP agent upsIdentAgentSoftwareVersion<p>Update: 600</p>
Bypass Current Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output load in percent Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputPercentLoad.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output Power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output Voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input current Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input Frequency phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputFrequency.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>

Triggers

Name Description Expression Priority
UPS Bypassed phase {#SNMPINDEX} <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsBypassCurrent.[{#SNMPINDEX}].last()}<>0 or {HW UPS Legrand CS141:upsBypassPower.[{#SNMPINDEX}].last()}<>0</p><p>Recovery expression: </p> warning
UPS Input frequency outside nominal {#SNMPINDEX} <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}>53 or {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}<47</p><p>Recovery expression: </p> warning
UPS Overloaded phase {#SNMPINDEX} (>60%) <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsOutputPercentLoad.[{#SNMPINDEX}].last(#2)}>60</p><p>Recovery expression: </p> high
UPS Load Changed phase {#SNMPINDEX} (+/-300W) <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].change()}>300</p><p>Recovery expression: </p> information
UPS Low output power phase {#SNMPINDEX} (<10 W) <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].last()}<10</p><p>Recovery expression: </p> warning
UPS Power Voltage outside nominal phase {#SNMPINDEX} <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}<200 or {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}>250</p><p>Recovery expression: </p> high
UPS Bypassed phase {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsBypassCurrent.[{#SNMPINDEX}].last()}<>0 or {HW UPS Legrand CS141:upsBypassPower.[{#SNMPINDEX}].last()}<>0</p><p>Recovery expression: </p> warning
UPS Overloaded phase {#SNMPINDEX} (>60%) (LLD) <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsOutputPercentLoad.[{#SNMPINDEX}].last(#2)}>60</p><p>Recovery expression: </p> high
UPS Load Changed phase {#SNMPINDEX} (+/-300W) (LLD) <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].change()}>300</p><p>Recovery expression: </p> information
UPS Low output power phase {#SNMPINDEX} (<10 W) (LLD) <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].last()}<10</p><p>Recovery expression: </p> warning
UPS Power Voltage outside nominal phase {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}<200 or {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}>250</p><p>Recovery expression: </p> high
UPS Input frequency outside nominal {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}>53 or {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}<47</p><p>Recovery expression: </p> warning

HW UPS Legrand CS141

Overview

Template for monitoring UPS Legrand CS 141 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/

The content of template:

5 Applications: General, Health, Input, Output, Battery

18 Items:

Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage

Alarms present on {HOST.NAME}, Bypass Current, Bypass Power

Input line bads, Output Power, Output load in percent

Seconds on battery, Output Voltage

Estimated charge remaining, Battery voltage

Battery temperature, Device Version

Device Name, Device Model

13 Triggers and 4 Graphs

The template use SNMP agent v2. Assure that you set the community in template macros.

Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values

1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted

Send me what template you need, or if this template helped you, you can buy me one coffee :)

Upgraded template from Tudor Ticau

Author

Dusan Priechodsky

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
UPS Input Phases <p>-</p> SNMP agent upsInputFrequency<p>Update: 1h</p>
UPS Output Phses <p>-</p> SNMP agent upsOutputPower<p>Update: 1h</p>
UPS Bypass Phases <p>-</p> SNMP agent upsBypassCurrent<p>Update: 1h</p>

Items collected

Name Description Type Key and additional info
Device Model <p>The UPS Model designation.</p> SNMP agent upsIdentModel<p>Update: 86400</p>
Input line bads <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> SNMP agent upsInputLineBads<p>Update: 30</p>
Device Version <p>The UPS agent software version.</p> SNMP agent upsIdentAgentSoftwareVersion<p>Update: 600</p>
Alarms present on {HOST.NAME} <p>The present number of active alarm conditions.</p> SNMP agent upsAlarmsPresent<p>Update: 30</p>
Seconds on battery <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> SNMP agent upsSecondsOnBattery<p>Update: 30</p>
Device Location <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentLocation<p>Update: 600</p>
Device Name <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentName<p>Update: 600</p>
Device Uptime <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentUptime<p>Update: 1m</p>
Battery voltage <p>The magnitude of the present battery voltage.</p> SNMP agent upsBatteryVoltage<p>Update: 60</p>
Battery temperature <p>The ambient temperature at or near the UPS Battery casing.</p> SNMP agent upsBatteryTemperature<p>Update: 60</p>
Battery Status <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> SNMP agent upsBatteryStatus<p>Update: 30</p>
Estimated minutes remaining if no power <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> SNMP agent upsEstimatedMinutesRemaining<p>Update: 30</p>
Estimated charge remaining <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> SNMP agent upsEstimatedChargeRemaining<p>Update: 60</p>
Device Vendor <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentManufacturer<p>Update: 600</p>
Input current Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input Frequency phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputFrequency.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output load in percent Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputPercentLoad.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output Power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output Voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Current Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>

Triggers

Name Description Expression Priority
UPS Bypassed phase {#SNMPINDEX} <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> warning
UPS Input frequency outside nominal {#SNMPINDEX} <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> warning
UPS Overloaded phase {#SNMPINDEX} (>60%) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> high
UPS Load Changed phase {#SNMPINDEX} (+/-300W) <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> information
UPS Low output power phase {#SNMPINDEX} (<10 W) <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> warning
UPS Power Voltage outside nominal phase {#SNMPINDEX} <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> high
UPS Input frequency outside nominal {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> warning
UPS Overloaded phase {#SNMPINDEX} (>60%) (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> high
UPS Load Changed phase {#SNMPINDEX} (+/-300W) (LLD) <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> information
UPS Low output power phase {#SNMPINDEX} (<10 W) (LLD) <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> warning
UPS Power Voltage outside nominal phase {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> high
UPS Bypassed phase {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> warning

HW UPS Legrand CS141

Overview

Template for monitoring UPS Legrand CS 141 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/

The content of template:

5 Applications: General, Health, Input, Output, Battery

18 Items:

Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage

Alarms present on {HOST.NAME}, Bypass Current, Bypass Power

Input line bads, Output Power, Output load in percent

Seconds on battery, Output Voltage

Estimated charge remaining, Battery voltage

Battery temperature, Device Version

Device Name, Device Model

13 Triggers and 4 Graphs

The template use SNMP agent v2. Assure that you set the community in template macros.

Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values

1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted

Send me what template you need, or if this template helped you, you can buy me one coffee :)

Upgraded template from Tudor Ticau

Author

Dusan Priechodsky

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
UPS Input Phases <p>-</p> SNMP agent upsInputFrequency<p>Update: 1h</p>
UPS Output Phses <p>-</p> SNMP agent upsOutputPower<p>Update: 1h</p>
UPS Bypass Phases <p>-</p> SNMP agent upsBypassCurrent<p>Update: 1h</p>

Items collected

Name Description Type Key and additional info
Device Model <p>The UPS Model designation.</p> SNMP agent upsIdentModel<p>Update: 86400</p>
Input line bads <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> SNMP agent upsInputLineBads<p>Update: 30</p>
Device Version <p>The UPS agent software version.</p> SNMP agent upsIdentAgentSoftwareVersion<p>Update: 600</p>
Alarms present on {HOST.NAME} <p>The present number of active alarm conditions.</p> SNMP agent upsAlarmsPresent<p>Update: 30</p>
Seconds on battery <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> SNMP agent upsSecondsOnBattery<p>Update: 30</p>
Device Location <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentLocation<p>Update: 600</p>
Device Name <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentName<p>Update: 600</p>
Device Uptime <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentUptime<p>Update: 1m</p>
Battery voltage <p>The magnitude of the present battery voltage.</p> SNMP agent upsBatteryVoltage<p>Update: 60</p>
Battery temperature <p>The ambient temperature at or near the UPS Battery casing.</p> SNMP agent upsBatteryTemperature<p>Update: 60</p>
Battery Status <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> SNMP agent upsBatteryStatus<p>Update: 30</p>
Estimated minutes remaining if no power <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> SNMP agent upsEstimatedMinutesRemaining<p>Update: 30</p>
Estimated charge remaining <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> SNMP agent upsEstimatedChargeRemaining<p>Update: 60</p>
Device Vendor <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentManufacturer<p>Update: 600</p>
Input current Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input Frequency phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputFrequency.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Input voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsInputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output load in percent Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputPercentLoad.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output Power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Output Voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsOutputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Current Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Power Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>
Bypass Voltage Phase {#SNMPINDEX} <p>-</p> SNMP agent upsBypassVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p>

Triggers

Name Description Expression Priority
UPS Bypassed phase {#SNMPINDEX} <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> warning
UPS Input frequency outside nominal {#SNMPINDEX} <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> warning
UPS Overloaded phase {#SNMPINDEX} (>60%) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> high
UPS Load Changed phase {#SNMPINDEX} (+/-300W) <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> information
UPS Low output power phase {#SNMPINDEX} (<10 W) <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> warning
UPS Power Voltage outside nominal phase {#SNMPINDEX} <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> high
UPS Input frequency outside nominal {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> warning
UPS Overloaded phase {#SNMPINDEX} (>60%) (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> high
UPS Load Changed phase {#SNMPINDEX} (+/-300W) (LLD) <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> information
UPS Low output power phase {#SNMPINDEX} (<10 W) (LLD) <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> warning
UPS Power Voltage outside nominal phase {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> high
UPS Bypassed phase {#SNMPINDEX} (LLD) <p>-</p> <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> warning