Template for monitoring UPS Legrand CS 141 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/
The content of template:
5 Applications: General, Health, Input, Output, Battery
18 Items:
Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage
Alarms present on {HOST.NAME}, Bypass Current, Bypass Power
Input line bads, Output Power, Output load in percent
Seconds on battery, Output Voltage
Estimated charge remaining, Battery voltage
Battery temperature, Device Version
Device Name, Device Model
13 Triggers and 4 Graphs
The template use SNMP agent v2. Assure that you set the community in template macros.
Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values
1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted
Send me what template you need, or if this template helped you, you can buy me one coffee :)
Upgraded template from Tudor Ticau
Dusan Priechodsky
There are no macros links in this template.
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
UPS Bypass Phases | <p>-</p> | SNMP agent |
upsBypassCurrent<p>Update: 1h</p> |
UPS Output Phses | <p>-</p> | SNMP agent |
upsOutputPower<p>Update: 1h</p> |
UPS Input Phases | <p>-</p> | SNMP agent |
upsInputFrequency<p>Update: 1h</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
Seconds on battery | <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> | SNMP agent |
upsSecondsOnBattery<p>Update: 30</p> |
Device Vendor | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentManufacturer<p>Update: 600</p> |
Alarms present on {HOST.NAME} | <p>The present number of active alarm conditions.</p> | SNMP agent |
upsAlarmsPresent<p>Update: 30</p> |
Input line bads | <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> | SNMP agent |
upsInputLineBads<p>Update: 30</p> |
Battery Status | <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> | SNMP agent |
upsBatteryStatus<p>Update: 30</p> |
Device Uptime | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentUptime<p>Update: 1m</p> |
Battery voltage | <p>The magnitude of the present battery voltage.</p> | SNMP agent |
upsBatteryVoltage<p>Update: 60</p> |
Device Name | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentName<p>Update: 600</p> |
Estimated minutes remaining if no power | <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> | SNMP agent |
upsEstimatedMinutesRemaining<p>Update: 30</p> |
Device Model | <p>The UPS Model designation.</p> | SNMP agent |
upsIdentModel<p>Update: 86400</p> |
Device Location | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentLocation<p>Update: 600</p> |
Battery temperature | <p>The ambient temperature at or near the UPS Battery casing.</p> | SNMP agent |
upsBatteryTemperature<p>Update: 60</p> |
Estimated charge remaining | <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> | SNMP agent |
upsEstimatedChargeRemaining<p>Update: 60</p> |
Device Version | <p>The UPS agent software version.</p> | SNMP agent |
upsIdentAgentSoftwareVersion<p>Update: 600</p> |
Bypass Current Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output load in percent Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputPercentLoad.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output Power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output Voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input current Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input Frequency phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputFrequency.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
UPS Bypassed phase {#SNMPINDEX} | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsBypassCurrent.[{#SNMPINDEX}].last()}<>0 or {HW UPS Legrand CS141:upsBypassPower.[{#SNMPINDEX}].last()}<>0</p><p>Recovery expression: </p> | warning |
UPS Input frequency outside nominal {#SNMPINDEX} | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}>53 or {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}<47</p><p>Recovery expression: </p> | warning |
UPS Overloaded phase {#SNMPINDEX} (>60%) | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputPercentLoad.[{#SNMPINDEX}].last(#2)}>60</p><p>Recovery expression: </p> | high |
UPS Load Changed phase {#SNMPINDEX} (+/-300W) | <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].change()}>300</p><p>Recovery expression: </p> | information |
UPS Low output power phase {#SNMPINDEX} (<10 W) | <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].last()}<10</p><p>Recovery expression: </p> | warning |
UPS Power Voltage outside nominal phase {#SNMPINDEX} | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}<200 or {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}>250</p><p>Recovery expression: </p> | high |
UPS Bypassed phase {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsBypassCurrent.[{#SNMPINDEX}].last()}<>0 or {HW UPS Legrand CS141:upsBypassPower.[{#SNMPINDEX}].last()}<>0</p><p>Recovery expression: </p> | warning |
UPS Overloaded phase {#SNMPINDEX} (>60%) (LLD) | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputPercentLoad.[{#SNMPINDEX}].last(#2)}>60</p><p>Recovery expression: </p> | high |
UPS Load Changed phase {#SNMPINDEX} (+/-300W) (LLD) | <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].change()}>300</p><p>Recovery expression: </p> | information |
UPS Low output power phase {#SNMPINDEX} (<10 W) (LLD) | <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputPower.[{#SNMPINDEX}].last()}<10</p><p>Recovery expression: </p> | warning |
UPS Power Voltage outside nominal phase {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}<200 or {HW UPS Legrand CS141:upsOutputVoltage.[{#SNMPINDEX}].last(#3)}>250</p><p>Recovery expression: </p> | high |
UPS Input frequency outside nominal {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}>53 or {HW UPS Legrand CS141:upsInputFrequency.[{#SNMPINDEX}].last()}<47</p><p>Recovery expression: </p> | warning |
Template for monitoring UPS Legrand CS 141 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/
The content of template:
5 Applications: General, Health, Input, Output, Battery
18 Items:
Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage
Alarms present on {HOST.NAME}, Bypass Current, Bypass Power
Input line bads, Output Power, Output load in percent
Seconds on battery, Output Voltage
Estimated charge remaining, Battery voltage
Battery temperature, Device Version
Device Name, Device Model
13 Triggers and 4 Graphs
The template use SNMP agent v2. Assure that you set the community in template macros.
Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values
1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted
Send me what template you need, or if this template helped you, you can buy me one coffee :)
Upgraded template from Tudor Ticau
Dusan Priechodsky
There are no macros links in this template.
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
UPS Input Phases | <p>-</p> | SNMP agent |
upsInputFrequency<p>Update: 1h</p> |
UPS Output Phses | <p>-</p> | SNMP agent |
upsOutputPower<p>Update: 1h</p> |
UPS Bypass Phases | <p>-</p> | SNMP agent |
upsBypassCurrent<p>Update: 1h</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
Device Model | <p>The UPS Model designation.</p> | SNMP agent |
upsIdentModel<p>Update: 86400</p> |
Input line bads | <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> | SNMP agent |
upsInputLineBads<p>Update: 30</p> |
Device Version | <p>The UPS agent software version.</p> | SNMP agent |
upsIdentAgentSoftwareVersion<p>Update: 600</p> |
Alarms present on {HOST.NAME} | <p>The present number of active alarm conditions.</p> | SNMP agent |
upsAlarmsPresent<p>Update: 30</p> |
Seconds on battery | <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> | SNMP agent |
upsSecondsOnBattery<p>Update: 30</p> |
Device Location | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentLocation<p>Update: 600</p> |
Device Name | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentName<p>Update: 600</p> |
Device Uptime | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentUptime<p>Update: 1m</p> |
Battery voltage | <p>The magnitude of the present battery voltage.</p> | SNMP agent |
upsBatteryVoltage<p>Update: 60</p> |
Battery temperature | <p>The ambient temperature at or near the UPS Battery casing.</p> | SNMP agent |
upsBatteryTemperature<p>Update: 60</p> |
Battery Status | <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> | SNMP agent |
upsBatteryStatus<p>Update: 30</p> |
Estimated minutes remaining if no power | <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> | SNMP agent |
upsEstimatedMinutesRemaining<p>Update: 30</p> |
Estimated charge remaining | <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> | SNMP agent |
upsEstimatedChargeRemaining<p>Update: 60</p> |
Device Vendor | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentManufacturer<p>Update: 600</p> |
Input current Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input Frequency phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputFrequency.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output load in percent Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputPercentLoad.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output Power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output Voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Current Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
UPS Bypassed phase {#SNMPINDEX} | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> | warning |
UPS Input frequency outside nominal {#SNMPINDEX} | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> | warning |
UPS Overloaded phase {#SNMPINDEX} (>60%) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> | high |
UPS Load Changed phase {#SNMPINDEX} (+/-300W) | <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> | <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> | information |
UPS Low output power phase {#SNMPINDEX} (<10 W) | <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> | warning |
UPS Power Voltage outside nominal phase {#SNMPINDEX} | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> | high |
UPS Input frequency outside nominal {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> | warning |
UPS Overloaded phase {#SNMPINDEX} (>60%) (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> | high |
UPS Load Changed phase {#SNMPINDEX} (+/-300W) (LLD) | <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> | <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> | information |
UPS Low output power phase {#SNMPINDEX} (<10 W) (LLD) | <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> | warning |
UPS Power Voltage outside nominal phase {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> | high |
UPS Bypassed phase {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> | warning |
Template for monitoring UPS Legrand CS 141 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/
The content of template:
5 Applications: General, Health, Input, Output, Battery
18 Items:
Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage
Alarms present on {HOST.NAME}, Bypass Current, Bypass Power
Input line bads, Output Power, Output load in percent
Seconds on battery, Output Voltage
Estimated charge remaining, Battery voltage
Battery temperature, Device Version
Device Name, Device Model
13 Triggers and 4 Graphs
The template use SNMP agent v2. Assure that you set the community in template macros.
Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values
1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted
Send me what template you need, or if this template helped you, you can buy me one coffee :)
Upgraded template from Tudor Ticau
Dusan Priechodsky
There are no macros links in this template.
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
UPS Input Phases | <p>-</p> | SNMP agent |
upsInputFrequency<p>Update: 1h</p> |
UPS Output Phses | <p>-</p> | SNMP agent |
upsOutputPower<p>Update: 1h</p> |
UPS Bypass Phases | <p>-</p> | SNMP agent |
upsBypassCurrent<p>Update: 1h</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
Device Model | <p>The UPS Model designation.</p> | SNMP agent |
upsIdentModel<p>Update: 86400</p> |
Input line bads | <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> | SNMP agent |
upsInputLineBads<p>Update: 30</p> |
Device Version | <p>The UPS agent software version.</p> | SNMP agent |
upsIdentAgentSoftwareVersion<p>Update: 600</p> |
Alarms present on {HOST.NAME} | <p>The present number of active alarm conditions.</p> | SNMP agent |
upsAlarmsPresent<p>Update: 30</p> |
Seconds on battery | <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> | SNMP agent |
upsSecondsOnBattery<p>Update: 30</p> |
Device Location | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentLocation<p>Update: 600</p> |
Device Name | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentName<p>Update: 600</p> |
Device Uptime | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentUptime<p>Update: 1m</p> |
Battery voltage | <p>The magnitude of the present battery voltage.</p> | SNMP agent |
upsBatteryVoltage<p>Update: 60</p> |
Battery temperature | <p>The ambient temperature at or near the UPS Battery casing.</p> | SNMP agent |
upsBatteryTemperature<p>Update: 60</p> |
Battery Status | <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> | SNMP agent |
upsBatteryStatus<p>Update: 30</p> |
Estimated minutes remaining if no power | <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> | SNMP agent |
upsEstimatedMinutesRemaining<p>Update: 30</p> |
Estimated charge remaining | <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> | SNMP agent |
upsEstimatedChargeRemaining<p>Update: 60</p> |
Device Vendor | <p>The name of the UPS manufacturer.</p> | SNMP agent |
upsIdentManufacturer<p>Update: 600</p> |
Input current Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input Frequency phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputFrequency.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Input voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsInputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output load in percent Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputPercentLoad.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output Power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Output Voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsOutputVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Current Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassCurrent.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Power Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassPower.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Bypass Voltage Phase {#SNMPINDEX} | <p>-</p> | SNMP agent |
upsBypassVoltage.[{#SNMPINDEX}]<p>Update: 1m</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
UPS Bypassed phase {#SNMPINDEX} | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> | warning |
UPS Input frequency outside nominal {#SNMPINDEX} | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> | warning |
UPS Overloaded phase {#SNMPINDEX} (>60%) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> | high |
UPS Load Changed phase {#SNMPINDEX} (+/-300W) | <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> | <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> | information |
UPS Low output power phase {#SNMPINDEX} (<10 W) | <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> | warning |
UPS Power Voltage outside nominal phase {#SNMPINDEX} | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> | high |
UPS Input frequency outside nominal {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])>53 or last(/HW UPS Legrand CS141/upsInputFrequency.[{#SNMPINDEX}])<47</p><p>Recovery expression: </p> | warning |
UPS Overloaded phase {#SNMPINDEX} (>60%) (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPercentLoad.[{#SNMPINDEX}],#2)>60</p><p>Recovery expression: </p> | high |
UPS Load Changed phase {#SNMPINDEX} (+/-300W) (LLD) | <p>On {HOST.NAME} we detect a big load change - the power output differential is over 300W</p> | <p>Expression: change(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])>300</p><p>Recovery expression: </p> | information |
UPS Low output power phase {#SNMPINDEX} (<10 W) (LLD) | <p>The output power for {HOST.NAME} is under {ITEM.VALUE}. Take actions to prevent this in future</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputPower.[{#SNMPINDEX}])<10</p><p>Recovery expression: </p> | warning |
UPS Power Voltage outside nominal phase {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)<200 or last(/HW UPS Legrand CS141/upsOutputVoltage.[{#SNMPINDEX}],#3)>250</p><p>Recovery expression: </p> | high |
UPS Bypassed phase {#SNMPINDEX} (LLD) | <p>-</p> | <p>Expression: last(/HW UPS Legrand CS141/upsBypassCurrent.[{#SNMPINDEX}])<>0 or last(/HW UPS Legrand CS141/upsBypassPower.[{#SNMPINDEX}])<>0</p><p>Recovery expression: </p> | warning |