Available versions




Halley UPS Legrand cs121

Overview

Template for monitoring UPS Legrand CS 121 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/

The content of template:

5 Applications: General, Health, Input, Output, Battery

18 Items:

Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage

Alarms present on {HOST.NAME}, Bypass Current, Bypass Power

Input line bads, Output Power, Output load in percent

Seconds on battery, Output Voltage

Estimated charge remaining, Battery voltage

Battery temperature, Device Version

Device Name, Device Model

13 Triggers and 4 Graphs

The template use SNMP agent v2. Assure that you set the community in template macros.

Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values

1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted

Author

Tudor Ticau

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> MonitorZabbix Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Device Model <p>The UPS Model designation.</p> SNMP agent upsIdentModel<p>Update: 86400</p>
Seconds on battery <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> SNMP agent upsSecondsOnBattery<p>Update: 30</p>
Output Voltage <p>The present output voltage.</p> SNMP agent upsOutputVoltage.1<p>Update: 30</p>
Bypass Voltage <p>An automatic bypass of voltage is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards</p> SNMP agent upsBypassVoltage.1<p>Update: 30</p>
Bypass Current <p>An automatic bypass of voltage is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards. This item show the amperage that we have in bypass time</p> SNMP agent upsBypassCurrent.1<p>Update: 30</p>
Estimated charge remaining <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> SNMP agent upsEstimatedChargeRemaining<p>Update: 60</p>
Device Name <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentManufacturer<p>Update: 600</p>
Input voltage <p>The magnitude of the present input voltage.</p> SNMP agent upsInputVoltage.1<p>Update: 30</p>
Output Power <p>The present output true power.</p> SNMP agent upsOutputPower.1<p>Update: 30</p>
Device Version <p>The UPS agent software version.</p> SNMP agent upsIdentAgentSoftwareVersion<p>Update: 600</p>
Battery Status <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> SNMP agent upsBatteryStatus<p>Update: 30</p>
Alarms present on {HOST.NAME} <p>The present number of active alarm conditions.</p> SNMP agent upsAlarmsPresent<p>Update: 30</p>
Battery temperature <p>The ambient temperature at or near the UPS Battery casing.</p> SNMP agent upsBatteryTemperature<p>Update: 60</p>
Input line bads <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> SNMP agent upsInputLineBads<p>Update: 30</p>
Output load in percent <p>The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.</p> SNMP agent upsOutputPercentLoad.1<p>Update: 30</p>
Battery voltage <p>The magnitude of the present battery voltage.</p> SNMP agent upsBatteryVoltage<p>Update: 60</p>
Bypass Power <p>An automatic bypass is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards This item show the power that we have in bypass time</p> SNMP agent upsBypassPower.1<p>Update: 30</p>
Estimated minutes remaining if no power <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> SNMP agent upsEstimatedMinutesRemaining<p>Update: 30</p>

Triggers

There are no triggers in this template.

Halley UPS Legrand cs121

Overview

Template for monitoring UPS Legrand CS 121 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/

The content of template:

5 Applications: General, Health, Input, Output, Battery

18 Items:

Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage

Alarms present on {HOST.NAME}, Bypass Current, Bypass Power

Input line bads, Output Power, Output load in percent

Seconds on battery, Output Voltage

Estimated charge remaining, Battery voltage

Battery temperature, Device Version

Device Name, Device Model

13 Triggers and 4 Graphs

The template use SNMP agent v2. Assure that you set the community in template macros.

Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values

1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted

Author

Tudor Ticau

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> MonitorZabbix Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Device Name <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentManufacturer<p>Update: 600</p>
Battery temperature <p>The ambient temperature at or near the UPS Battery casing.</p> SNMP agent upsBatteryTemperature<p>Update: 60</p>
Input voltage <p>The magnitude of the present input voltage.</p> SNMP agent upsInputVoltage.1<p>Update: 30</p>
Output Voltage <p>The present output voltage.</p> SNMP agent upsOutputVoltage.1<p>Update: 30</p>
Battery voltage <p>The magnitude of the present battery voltage.</p> SNMP agent upsBatteryVoltage<p>Update: 60</p>
Alarms present on {HOST.NAME} <p>The present number of active alarm conditions.</p> SNMP agent upsAlarmsPresent<p>Update: 30</p>
Estimated charge remaining <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> SNMP agent upsEstimatedChargeRemaining<p>Update: 60</p>
Output load in percent <p>The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.</p> SNMP agent upsOutputPercentLoad.1<p>Update: 30</p>
Input line bads <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> SNMP agent upsInputLineBads<p>Update: 30</p>
Device Model <p>The UPS Model designation.</p> SNMP agent upsIdentModel<p>Update: 86400</p>
Battery Status <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> SNMP agent upsBatteryStatus<p>Update: 30</p>
Output Power <p>The present output true power.</p> SNMP agent upsOutputPower.1<p>Update: 30</p>
Bypass Power <p>An automatic bypass is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards This item show the power that we have in bypass time</p> SNMP agent upsBypassPower.1<p>Update: 30</p>
Bypass Current <p>An automatic bypass of voltage is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards. This item show the amperage that we have in bypass time</p> SNMP agent upsBypassCurrent.1<p>Update: 30</p>
Seconds on battery <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> SNMP agent upsSecondsOnBattery<p>Update: 30</p>
Estimated minutes remaining if no power <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> SNMP agent upsEstimatedMinutesRemaining<p>Update: 30</p>
Bypass Voltage <p>An automatic bypass of voltage is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards</p> SNMP agent upsBypassVoltage.1<p>Update: 30</p>
Device Version <p>The UPS agent software version.</p> SNMP agent upsIdentAgentSoftwareVersion<p>Update: 600</p>

Triggers

There are no triggers in this template.

Halley UPS Legrand cs121

Overview

Template for monitoring UPS Legrand CS 121 (all models) with explanations and advices. The mibs are there: http://ups.legrand.com/software/

The content of template:

5 Applications: General, Health, Input, Output, Battery

18 Items:

Input voltage, Battery Status ,Estimated minutes remaining if no power , Bypass Voltage

Alarms present on {HOST.NAME}, Bypass Current, Bypass Power

Input line bads, Output Power, Output load in percent

Seconds on battery, Output Voltage

Estimated charge remaining, Battery voltage

Battery temperature, Device Version

Device Name, Device Model

13 Triggers and 4 Graphs

The template use SNMP agent v2. Assure that you set the community in template macros.

Assure also that in Administration -> General -> Value mapping you have under APC Battery Status next values

1 ⇒ unknown
2 ⇒ batteryNormal
3 ⇒ batteryLow
4 ⇒ batteryDepleted

Author

Tudor Ticau

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> MonitorZabbix Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Device Name <p>The name of the UPS manufacturer.</p> SNMP agent upsIdentManufacturer<p>Update: 600</p>
Battery temperature <p>The ambient temperature at or near the UPS Battery casing.</p> SNMP agent upsBatteryTemperature<p>Update: 60</p>
Input voltage <p>The magnitude of the present input voltage.</p> SNMP agent upsInputVoltage.1<p>Update: 30</p>
Output Voltage <p>The present output voltage.</p> SNMP agent upsOutputVoltage.1<p>Update: 30</p>
Battery voltage <p>The magnitude of the present battery voltage.</p> SNMP agent upsBatteryVoltage<p>Update: 60</p>
Alarms present on {HOST.NAME} <p>The present number of active alarm conditions.</p> SNMP agent upsAlarmsPresent<p>Update: 30</p>
Estimated charge remaining <p>An estimate of the battery charge remaining expressed as a percent of full charge.</p> SNMP agent upsEstimatedChargeRemaining<p>Update: 60</p>
Output load in percent <p>The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.</p> SNMP agent upsOutputPercentLoad.1<p>Update: 30</p>
Input line bads <p>A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. A big number show problems with the electricity power where your UPS is connected</p> SNMP agent upsInputLineBads<p>Update: 30</p>
Device Model <p>The UPS Model designation.</p> SNMP agent upsIdentModel<p>Update: 86400</p>
Battery Status <p>The indication of the capacity remaining in the UPS system’s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).</p> SNMP agent upsBatteryStatus<p>Update: 30</p>
Output Power <p>The present output true power.</p> SNMP agent upsOutputPower.1<p>Update: 30</p>
Bypass Power <p>An automatic bypass is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards This item show the power that we have in bypass time</p> SNMP agent upsBypassPower.1<p>Update: 30</p>
Bypass Current <p>An automatic bypass of voltage is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards. This item show the amperage that we have in bypass time</p> SNMP agent upsBypassCurrent.1<p>Update: 30</p>
Seconds on battery <p>If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.</p> SNMP agent upsSecondsOnBattery<p>Update: 30</p>
Estimated minutes remaining if no power <p>An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.</p> SNMP agent upsEstimatedMinutesRemaining<p>Update: 30</p>
Bypass Voltage <p>An automatic bypass of voltage is used by the UPS to switch its load to the mains if it experiences an overload or internal failure. In other words, this mean that UPS has some problems and switch to the main (wall) power. So, if we have bypass - in bypass time our servers are connected directly to the line power - and are exposed to all electricity hazards</p> SNMP agent upsBypassVoltage.1<p>Update: 30</p>
Device Version <p>The UPS agent software version.</p> SNMP agent upsIdentAgentSoftwareVersion<p>Update: 600</p>