Hi,
Here is a template for HP PDU’s
There are mostly traps items but also some polling items.
SNMPv2.
Triggers are also include.
You need to put your SNMP community in macro.
Thanks.
Vincent MATIAS
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | `` | Text macro |
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Trap Total Power Critical | <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Power Critical”]<p>Update: 0</p> |
Load Segment 3 | <p>-</p> | SNMP agent |
breakerCurrent.1.3<p>Update: 30s</p> |
Trap fallback | <p>-</p> | SNMP trap |
snmptrap.fallback<p>Update: 0</p> |
Percent Load Segment 3 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.3<p>Update: 30s</p> |
Total Power | <p>-</p> | SNMP agent |
pduOutputPower.1<p>Update: 30s</p> |
{HOST.NAME} Status | <p>-</p> | SNMP agent |
pduStatus.1<p>Update: 1m</p> |
Trap PDU Communication Lost | <p>Connection between the daisy-chained PDUs is lost.</p> | SNMP trap |
snmptrap[“PDU Communication Lost”]<p>Update: 0</p> |
PDU Name | <p>-</p> | SNMP agent |
pduName.1<p>Update: 1h</p> |
Trap Total Load Critical | <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Load Critical”]<p>Update: 0</p> |
Total Heat | <p>-</p> | SNMP agent |
pduOutputHeat.1<p>Update: 30s</p> |
Trap Total Heat Critical | <p>The heat created by the load attached to this PDU has exceeded the set threshold</p> | SNMP trap |
snmptrap[“Total Heat Critical”]<p>Update: 0</p> |
Trap Voltage High Warning | <p>The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage</p> | SNMP trap |
snmptrap[“Voltage High Warning”]<p>Update: 0</p> |
Trap Current Warning | <p>Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Current Warning”]<p>Update: 0</p> |
Trap Total Load Warning | <p>The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Load Warning”]<p>Update: 0</p> |
Trap Voltage Low Critical | <p>The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.</p> | SNMP trap |
snmptrap[“Voltage Low Critical”]<p>Update: 0</p> |
Trap Total Heat Warning | <p>The heat created by the load attached to this PDU has reached a threshold</p> | SNMP trap |
snmptrap[“Total Heat Warning”]<p>Update: 0</p> |
Load Segment 1 | <p>-</p> | SNMP agent |
breakerCurrent.1.1<p>Update: 30s</p> |
Trap Load Warning | <p>Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Load Warning”]<p>Update: 0</p> |
Trap Total Power Warning | <p>The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Power Warning”]<p>Update: 0</p> |
Trap Voltage Low Warning | <p>The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage</p> | SNMP trap |
snmptrap[“Voltage Low Warning”]<p>Update: 0</p> |
Trap Voltage High Critical | <p>The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage</p> | SNMP trap |
snmptrap[“Voltage High Critical”]<p>Update: 0</p> |
Voltage Segment 3 | <p>-</p> | SNMP agent |
breakerVoltage.1.3<p>Update: 30s</p> |
Voltage Segment 2 | <p>-</p> | SNMP agent |
breakerVoltage.1.2<p>Update: 30s</p> |
Trap Load Critical | <p>The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker</p> | SNMP trap |
snmptrap[“Load Critical”]<p>Update: 0</p> |
Percent Load Segment 2 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.2<p>Update: 30s</p> |
Voltage Segment 1 | <p>-</p> | SNMP agent |
breakerVoltage.1.1<p>Update: 30s</p> |
Load Segment 2 | <p>-</p> | SNMP agent |
breakerCurrent.1.2<p>Update: 30s</p> |
Trap Current Critical | <p>Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Current Critical”]<p>Update: 0</p> |
Percent Load Segment 1 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.1<p>Update: 30s</p> |
Total Load | <p>-</p> | SNMP agent |
pduOutputLoad.1<p>Update: 30s</p> |
There are no triggers in this template.
Hi,
Here is a template for HP PDU’s
There are mostly traps items but also some polling items.
SNMPv2.
Triggers are also include.
You need to put your SNMP community in macro.
Thanks.
Vincent MATIAS
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | `` | Text macro |
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Trap Load Critical | <p>The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker</p> | SNMP trap |
snmptrap[“Load Critical”]<p>Update: 0</p> |
Trap Total Heat Critical | <p>The heat created by the load attached to this PDU has exceeded the set threshold</p> | SNMP trap |
snmptrap[“Total Heat Critical”]<p>Update: 0</p> |
Voltage Segment 3 | <p>-</p> | SNMP agent |
breakerVoltage.1.3<p>Update: 30s</p> |
PDU Name | <p>-</p> | SNMP agent |
pduName.1<p>Update: 1h</p> |
Trap Voltage Low Critical | <p>The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.</p> | SNMP trap |
snmptrap[“Voltage Low Critical”]<p>Update: 0</p> |
Load Segment 1 | <p>-</p> | SNMP agent |
breakerCurrent.1.1<p>Update: 30s</p> |
Total Power | <p>-</p> | SNMP agent |
pduOutputPower.1<p>Update: 30s</p> |
Voltage Segment 1 | <p>-</p> | SNMP agent |
breakerVoltage.1.1<p>Update: 30s</p> |
Total Load | <p>-</p> | SNMP agent |
pduOutputLoad.1<p>Update: 30s</p> |
Load Segment 3 | <p>-</p> | SNMP agent |
breakerCurrent.1.3<p>Update: 30s</p> |
Trap Voltage High Warning | <p>The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage</p> | SNMP trap |
snmptrap[“Voltage High Warning”]<p>Update: 0</p> |
Trap Total Load Warning | <p>The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Load Warning”]<p>Update: 0</p> |
Voltage Segment 2 | <p>-</p> | SNMP agent |
breakerVoltage.1.2<p>Update: 30s</p> |
Trap Current Critical | <p>Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Current Critical”]<p>Update: 0</p> |
Percent Load Segment 1 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.1<p>Update: 30s</p> |
Trap Total Power Warning | <p>The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Power Warning”]<p>Update: 0</p> |
Percent Load Segment 2 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.2<p>Update: 30s</p> |
Trap Current Warning | <p>Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Current Warning”]<p>Update: 0</p> |
Trap PDU Communication Lost | <p>Connection between the daisy-chained PDUs is lost.</p> | SNMP trap |
snmptrap[“PDU Communication Lost”]<p>Update: 0</p> |
Trap fallback | <p>-</p> | SNMP trap |
snmptrap.fallback<p>Update: 0</p> |
Trap Total Heat Warning | <p>The heat created by the load attached to this PDU has reached a threshold</p> | SNMP trap |
snmptrap[“Total Heat Warning”]<p>Update: 0</p> |
Trap Voltage Low Warning | <p>The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage</p> | SNMP trap |
snmptrap[“Voltage Low Warning”]<p>Update: 0</p> |
Total Heat | <p>-</p> | SNMP agent |
pduOutputHeat.1<p>Update: 30s</p> |
Trap Total Load Critical | <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Load Critical”]<p>Update: 0</p> |
Trap Load Warning | <p>Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Load Warning”]<p>Update: 0</p> |
Trap Total Power Critical | <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Power Critical”]<p>Update: 0</p> |
Trap Voltage High Critical | <p>The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage</p> | SNMP trap |
snmptrap[“Voltage High Critical”]<p>Update: 0</p> |
{HOST.NAME} Status | <p>-</p> | SNMP agent |
pduStatus.1<p>Update: 1m</p> |
Percent Load Segment 3 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.3<p>Update: 30s</p> |
Load Segment 2 | <p>-</p> | SNMP agent |
breakerCurrent.1.2<p>Update: 30s</p> |
There are no triggers in this template.
Hi,
Here is a template for HP PDU’s
There are mostly traps items but also some polling items.
SNMPv2.
Triggers are also include.
You need to put your SNMP community in macro.
Thanks.
Vincent MATIAS
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | `` | Text macro |
There are no template links in this template.
There are no discovery rules in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Trap Load Critical | <p>The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker</p> | SNMP trap |
snmptrap[“Load Critical”]<p>Update: 0</p> |
Trap Total Heat Critical | <p>The heat created by the load attached to this PDU has exceeded the set threshold</p> | SNMP trap |
snmptrap[“Total Heat Critical”]<p>Update: 0</p> |
Voltage Segment 3 | <p>-</p> | SNMP agent |
breakerVoltage.1.3<p>Update: 30s</p> |
PDU Name | <p>-</p> | SNMP agent |
pduName.1<p>Update: 1h</p> |
Trap Voltage Low Critical | <p>The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.</p> | SNMP trap |
snmptrap[“Voltage Low Critical”]<p>Update: 0</p> |
Load Segment 1 | <p>-</p> | SNMP agent |
breakerCurrent.1.1<p>Update: 30s</p> |
Total Power | <p>-</p> | SNMP agent |
pduOutputPower.1<p>Update: 30s</p> |
Voltage Segment 1 | <p>-</p> | SNMP agent |
breakerVoltage.1.1<p>Update: 30s</p> |
Total Load | <p>-</p> | SNMP agent |
pduOutputLoad.1<p>Update: 30s</p> |
Load Segment 3 | <p>-</p> | SNMP agent |
breakerCurrent.1.3<p>Update: 30s</p> |
Trap Voltage High Warning | <p>The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage</p> | SNMP trap |
snmptrap[“Voltage High Warning”]<p>Update: 0</p> |
Trap Total Load Warning | <p>The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Load Warning”]<p>Update: 0</p> |
Voltage Segment 2 | <p>-</p> | SNMP agent |
breakerVoltage.1.2<p>Update: 30s</p> |
Trap Current Critical | <p>Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Current Critical”]<p>Update: 0</p> |
Percent Load Segment 1 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.1<p>Update: 30s</p> |
Trap Total Power Warning | <p>The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Power Warning”]<p>Update: 0</p> |
Percent Load Segment 2 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.2<p>Update: 30s</p> |
Trap Current Warning | <p>Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Current Warning”]<p>Update: 0</p> |
Trap PDU Communication Lost | <p>Connection between the daisy-chained PDUs is lost.</p> | SNMP trap |
snmptrap[“PDU Communication Lost”]<p>Update: 0</p> |
Trap fallback | <p>-</p> | SNMP trap |
snmptrap.fallback<p>Update: 0</p> |
Trap Total Heat Warning | <p>The heat created by the load attached to this PDU has reached a threshold</p> | SNMP trap |
snmptrap[“Total Heat Warning”]<p>Update: 0</p> |
Trap Voltage Low Warning | <p>The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage</p> | SNMP trap |
snmptrap[“Voltage Low Warning”]<p>Update: 0</p> |
Total Heat | <p>-</p> | SNMP agent |
pduOutputHeat.1<p>Update: 30s</p> |
Trap Total Load Critical | <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Load Critical”]<p>Update: 0</p> |
Trap Load Warning | <p>Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> | SNMP trap |
snmptrap[“Load Warning”]<p>Update: 0</p> |
Trap Total Power Critical | <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> | SNMP trap |
snmptrap[“Total Power Critical”]<p>Update: 0</p> |
Trap Voltage High Critical | <p>The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage</p> | SNMP trap |
snmptrap[“Voltage High Critical”]<p>Update: 0</p> |
{HOST.NAME} Status | <p>-</p> | SNMP agent |
pduStatus.1<p>Update: 1m</p> |
Percent Load Segment 3 | <p>-</p> | SNMP agent |
breakerPercentLoad.1.3<p>Update: 30s</p> |
Load Segment 2 | <p>-</p> | SNMP agent |
breakerCurrent.1.2<p>Update: 30s</p> |
There are no triggers in this template.