Available versions




Monitoring PDU

Overview

Hi,

Here is a template for HP PDU’s

There are mostly traps items but also some polling items.

SNMPv2.

Triggers are also include.

You need to put your SNMP community in macro.

Thanks.

Author

Vincent MATIAS

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> `` Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Trap Total Power Critical <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Power Critical”]<p>Update: 0</p>
Load Segment 3 <p>-</p> SNMP agent breakerCurrent.1.3<p>Update: 30s</p>
Trap fallback <p>-</p> SNMP trap snmptrap.fallback<p>Update: 0</p>
Percent Load Segment 3 <p>-</p> SNMP agent breakerPercentLoad.1.3<p>Update: 30s</p>
Total Power <p>-</p> SNMP agent pduOutputPower.1<p>Update: 30s</p>
{HOST.NAME} Status <p>-</p> SNMP agent pduStatus.1<p>Update: 1m</p>
Trap PDU Communication Lost <p>Connection between the daisy-chained PDUs is lost.</p> SNMP trap snmptrap[“PDU Communication Lost”]<p>Update: 0</p>
PDU Name <p>-</p> SNMP agent pduName.1<p>Update: 1h</p>
Trap Total Load Critical <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Load Critical”]<p>Update: 0</p>
Total Heat <p>-</p> SNMP agent pduOutputHeat.1<p>Update: 30s</p>
Trap Total Heat Critical <p>The heat created by the load attached to this PDU has exceeded the set threshold</p> SNMP trap snmptrap[“Total Heat Critical”]<p>Update: 0</p>
Trap Voltage High Warning <p>The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage</p> SNMP trap snmptrap[“Voltage High Warning”]<p>Update: 0</p>
Trap Current Warning <p>Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Current Warning”]<p>Update: 0</p>
Trap Total Load Warning <p>The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Load Warning”]<p>Update: 0</p>
Trap Voltage Low Critical <p>The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.</p> SNMP trap snmptrap[“Voltage Low Critical”]<p>Update: 0</p>
Trap Total Heat Warning <p>The heat created by the load attached to this PDU has reached a threshold</p> SNMP trap snmptrap[“Total Heat Warning”]<p>Update: 0</p>
Load Segment 1 <p>-</p> SNMP agent breakerCurrent.1.1<p>Update: 30s</p>
Trap Load Warning <p>Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Load Warning”]<p>Update: 0</p>
Trap Total Power Warning <p>The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Power Warning”]<p>Update: 0</p>
Trap Voltage Low Warning <p>The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage</p> SNMP trap snmptrap[“Voltage Low Warning”]<p>Update: 0</p>
Trap Voltage High Critical <p>The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage</p> SNMP trap snmptrap[“Voltage High Critical”]<p>Update: 0</p>
Voltage Segment 3 <p>-</p> SNMP agent breakerVoltage.1.3<p>Update: 30s</p>
Voltage Segment 2 <p>-</p> SNMP agent breakerVoltage.1.2<p>Update: 30s</p>
Trap Load Critical <p>The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker</p> SNMP trap snmptrap[“Load Critical”]<p>Update: 0</p>
Percent Load Segment 2 <p>-</p> SNMP agent breakerPercentLoad.1.2<p>Update: 30s</p>
Voltage Segment 1 <p>-</p> SNMP agent breakerVoltage.1.1<p>Update: 30s</p>
Load Segment 2 <p>-</p> SNMP agent breakerCurrent.1.2<p>Update: 30s</p>
Trap Current Critical <p>Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Current Critical”]<p>Update: 0</p>
Percent Load Segment 1 <p>-</p> SNMP agent breakerPercentLoad.1.1<p>Update: 30s</p>
Total Load <p>-</p> SNMP agent pduOutputLoad.1<p>Update: 30s</p>

Triggers

There are no triggers in this template.

Monitoring PDU

Overview

Hi,

Here is a template for HP PDU’s

There are mostly traps items but also some polling items.

SNMPv2.

Triggers are also include.

You need to put your SNMP community in macro.

Thanks.

Author

Vincent MATIAS

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> `` Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Trap Load Critical <p>The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker</p> SNMP trap snmptrap[“Load Critical”]<p>Update: 0</p>
Trap Total Heat Critical <p>The heat created by the load attached to this PDU has exceeded the set threshold</p> SNMP trap snmptrap[“Total Heat Critical”]<p>Update: 0</p>
Voltage Segment 3 <p>-</p> SNMP agent breakerVoltage.1.3<p>Update: 30s</p>
PDU Name <p>-</p> SNMP agent pduName.1<p>Update: 1h</p>
Trap Voltage Low Critical <p>The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.</p> SNMP trap snmptrap[“Voltage Low Critical”]<p>Update: 0</p>
Load Segment 1 <p>-</p> SNMP agent breakerCurrent.1.1<p>Update: 30s</p>
Total Power <p>-</p> SNMP agent pduOutputPower.1<p>Update: 30s</p>
Voltage Segment 1 <p>-</p> SNMP agent breakerVoltage.1.1<p>Update: 30s</p>
Total Load <p>-</p> SNMP agent pduOutputLoad.1<p>Update: 30s</p>
Load Segment 3 <p>-</p> SNMP agent breakerCurrent.1.3<p>Update: 30s</p>
Trap Voltage High Warning <p>The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage</p> SNMP trap snmptrap[“Voltage High Warning”]<p>Update: 0</p>
Trap Total Load Warning <p>The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Load Warning”]<p>Update: 0</p>
Voltage Segment 2 <p>-</p> SNMP agent breakerVoltage.1.2<p>Update: 30s</p>
Trap Current Critical <p>Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Current Critical”]<p>Update: 0</p>
Percent Load Segment 1 <p>-</p> SNMP agent breakerPercentLoad.1.1<p>Update: 30s</p>
Trap Total Power Warning <p>The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Power Warning”]<p>Update: 0</p>
Percent Load Segment 2 <p>-</p> SNMP agent breakerPercentLoad.1.2<p>Update: 30s</p>
Trap Current Warning <p>Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Current Warning”]<p>Update: 0</p>
Trap PDU Communication Lost <p>Connection between the daisy-chained PDUs is lost.</p> SNMP trap snmptrap[“PDU Communication Lost”]<p>Update: 0</p>
Trap fallback <p>-</p> SNMP trap snmptrap.fallback<p>Update: 0</p>
Trap Total Heat Warning <p>The heat created by the load attached to this PDU has reached a threshold</p> SNMP trap snmptrap[“Total Heat Warning”]<p>Update: 0</p>
Trap Voltage Low Warning <p>The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage</p> SNMP trap snmptrap[“Voltage Low Warning”]<p>Update: 0</p>
Total Heat <p>-</p> SNMP agent pduOutputHeat.1<p>Update: 30s</p>
Trap Total Load Critical <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Load Critical”]<p>Update: 0</p>
Trap Load Warning <p>Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Load Warning”]<p>Update: 0</p>
Trap Total Power Critical <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Power Critical”]<p>Update: 0</p>
Trap Voltage High Critical <p>The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage</p> SNMP trap snmptrap[“Voltage High Critical”]<p>Update: 0</p>
{HOST.NAME} Status <p>-</p> SNMP agent pduStatus.1<p>Update: 1m</p>
Percent Load Segment 3 <p>-</p> SNMP agent breakerPercentLoad.1.3<p>Update: 30s</p>
Load Segment 2 <p>-</p> SNMP agent breakerCurrent.1.2<p>Update: 30s</p>

Triggers

There are no triggers in this template.

Monitoring PDU

Overview

Hi,

Here is a template for HP PDU’s

There are mostly traps items but also some polling items.

SNMPv2.

Triggers are also include.

You need to put your SNMP community in macro.

Thanks.

Author

Vincent MATIAS

Macros used

Name Description Default Type
{$SNMP_COMMUNITY} <p>-</p> `` Text macro

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Trap Load Critical <p>The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker</p> SNMP trap snmptrap[“Load Critical”]<p>Update: 0</p>
Trap Total Heat Critical <p>The heat created by the load attached to this PDU has exceeded the set threshold</p> SNMP trap snmptrap[“Total Heat Critical”]<p>Update: 0</p>
Voltage Segment 3 <p>-</p> SNMP agent breakerVoltage.1.3<p>Update: 30s</p>
PDU Name <p>-</p> SNMP agent pduName.1<p>Update: 1h</p>
Trap Voltage Low Critical <p>The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.</p> SNMP trap snmptrap[“Voltage Low Critical”]<p>Update: 0</p>
Load Segment 1 <p>-</p> SNMP agent breakerCurrent.1.1<p>Update: 30s</p>
Total Power <p>-</p> SNMP agent pduOutputPower.1<p>Update: 30s</p>
Voltage Segment 1 <p>-</p> SNMP agent breakerVoltage.1.1<p>Update: 30s</p>
Total Load <p>-</p> SNMP agent pduOutputLoad.1<p>Update: 30s</p>
Load Segment 3 <p>-</p> SNMP agent breakerCurrent.1.3<p>Update: 30s</p>
Trap Voltage High Warning <p>The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage</p> SNMP trap snmptrap[“Voltage High Warning”]<p>Update: 0</p>
Trap Total Load Warning <p>The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Load Warning”]<p>Update: 0</p>
Voltage Segment 2 <p>-</p> SNMP agent breakerVoltage.1.2<p>Update: 30s</p>
Trap Current Critical <p>Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Current Critical”]<p>Update: 0</p>
Percent Load Segment 1 <p>-</p> SNMP agent breakerPercentLoad.1.1<p>Update: 30s</p>
Trap Total Power Warning <p>The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Power Warning”]<p>Update: 0</p>
Percent Load Segment 2 <p>-</p> SNMP agent breakerPercentLoad.1.2<p>Update: 30s</p>
Trap Current Warning <p>Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Current Warning”]<p>Update: 0</p>
Trap PDU Communication Lost <p>Connection between the daisy-chained PDUs is lost.</p> SNMP trap snmptrap[“PDU Communication Lost”]<p>Update: 0</p>
Trap fallback <p>-</p> SNMP trap snmptrap.fallback<p>Update: 0</p>
Trap Total Heat Warning <p>The heat created by the load attached to this PDU has reached a threshold</p> SNMP trap snmptrap[“Total Heat Warning”]<p>Update: 0</p>
Trap Voltage Low Warning <p>The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage</p> SNMP trap snmptrap[“Voltage Low Warning”]<p>Update: 0</p>
Total Heat <p>-</p> SNMP agent pduOutputHeat.1<p>Update: 30s</p>
Trap Total Load Critical <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Load Critical”]<p>Update: 0</p>
Trap Load Warning <p>Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker</p> SNMP trap snmptrap[“Load Warning”]<p>Update: 0</p>
Trap Total Power Critical <p>The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection</p> SNMP trap snmptrap[“Total Power Critical”]<p>Update: 0</p>
Trap Voltage High Critical <p>The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage</p> SNMP trap snmptrap[“Voltage High Critical”]<p>Update: 0</p>
{HOST.NAME} Status <p>-</p> SNMP agent pduStatus.1<p>Update: 1m</p>
Percent Load Segment 3 <p>-</p> SNMP agent breakerPercentLoad.1.3<p>Update: 30s</p>
Load Segment 2 <p>-</p> SNMP agent breakerCurrent.1.2<p>Update: 30s</p>

Triggers

There are no triggers in this template.