I have created a very detailed template for a Rack Mounted APC PDU. I spent a considerable amount of time digging through the MIB to obtain all the correct OID numbers pertaining to each Item for the PDU to use with SNMP. The template includes:
I hope you enjoy using this template as much as I have. You can tweak the Interval and History settings within each item per your needs. I have also included HOSTNAME calls in each Trigger to Identify the host that is causing the Trigger.
Chad Hoye
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | public |
Text macro |
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Outlets | <p>-</p> | SNMP agent |
rPDU2Outlet<p>Update: 3600</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
Phase 3 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.3<p>Update: 10s</p> |
Phase 1 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.1<p>Update: 10s</p> |
Phase 3 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.3<p>Update: 12h</p> |
System Up Time | <p>-</p> | SNMP agent |
sysUpTime.0<p>Update: 1h</p> |
Phase 1 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.1<p>Update: 12h</p> |
Load State | <p>Indicates the present load status of the Rack PDU.</p> | SNMP agent |
rPDU2DeviceStatusLoadState.1<p>Update: 10s</p> |
Max Phase Current Rating | <p>The maximum current rating, measured in Amps, for the Rack PDU</p> | SNMP agent |
rPDU2DevicePropertiesMaxPhaseCurrentRating.1<p>Update: 1h</p> |
Power Near Overload Threshold | <p>User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceConfigNearOverloadPowerThreshold.1<p>Update: 12h</p> |
Phase 2 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.2<p>Update: 12h</p> |
Model Number | <p>-</p> | SNMP agent |
rPDU2IdentModelNumber.1<p>Update: 12h</p> |
Phase 2 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.2<p>Update: 10s</p> |
Peak Power Timestamp | <p>-</p> | SNMP agent |
rPDU2DeviceStatusPeakPowerTimestamp.1<p>Update: 1h</p> |
Power Overload Threshold | <p>User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceConfigOverloadPowerThreshold.1<p>Update: 12h</p> |
Phase 3 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.3<p>Update: 10s</p> |
Phase 1 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.1<p>Update: 12h</p> |
Phase 2 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.2<p>Update: 12h</p> |
Phase Status Peak Current Timestamp | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrentTimestamp.1<p>Update: 1h</p> |
Phase 3 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.3<p>Update: 12h</p> |
Phase 1 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.1<p>Update: 12h</p> |
Location | <p>-</p> | SNMP agent |
rPDU2IdentLocation.1<p>Update: 1h</p> |
Phase 2 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.2<p>Update: 12h</p> |
Rack Inlet Temp | <p>Temperature of Air entering Rack</p> | SNMP agent |
rPDU2SensorTempHumidityStatusTempF.1<p>Update: 10s</p> |
Power Consumption | <p>The power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceStatusPower.1<p>Update: 10s</p> |
Phase 1 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.1<p>Update: 12h</p> |
Phase 3 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.3<p>Update: 12h</p> |
Phase 2 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.2<p>Update: 10s</p> |
Total Energy | <p>A user re-settable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.</p> | SNMP agent |
rPDU2DeviceStatusEnergy.1<p>Update: 1h</p> |
Serial Number | <p>-</p> | SNMP agent |
rPDU2IdentSerialNumber.1<p>Update: 12h</p> |
Phase 3 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.3<p>Update: 10s</p> |
Rack Inlet Humidity | <p>The Relative Humidity entering the rack</p> | SNMP agent |
rPDU2SensorTempHumidityStatusRelativeHumidity.1<p>Update: 10s</p> |
Phase 2 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.2<p>Update: 10s</p> |
Identification Name | <p>-</p> | SNMP agent |
rPDU2IdentName.1<p>Update: 1h</p> |
Phase 2 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.2<p>Update: 10s</p> |
Firmware Rev | <p>-</p> | SNMP agent |
rPDU2IdentFirmwareRev.1<p>Update: 12h</p> |
Phase 1 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.1<p>Update: 10s</p> |
Phase 3 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.3<p>Update: 10s</p> |
Phase 1 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.1<p>Update: 10s</p> |
Peak Power | <p>The peak power consumption of the Rack PDU load in hundredths of kilowatts.</p> | SNMP agent |
rPDU2DeviceStatusPeakPower.1<p>Update: 10s</p> |
Power Supply Alarm | <p>Indicates a power supply alarm is active when value equals alarm (2)</p> | SNMP agent |
rPDU2DeviceStatusPowerSupplyAlarm.1<p>Update: 10s</p> |
Outlet $1 Name | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedConfigName[{#SNMPINDEX}]<p>Update: 3600</p><p>LLD</p> |
Outlet $1 Bank | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedPropertiesBank[{#SNMPINDEX}]<p>Update: 86400</p><p>LLD</p> |
Outlet $1 State | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedStatusState[{#SNMPINDEX}]<p>Update: 60</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
Outlet {#SNMPVALUE} State Change | <p>-</p> | <p>Expression: {APC PDU:rPDU2OutletSwitchedStatusState[{#SNMPINDEX}].diff()}=1</p><p>Recovery expression: </p> | information |
Outlet {#SNMPVALUE} State Change (LLD) | <p>-</p> | <p>Expression: {APC PDU:rPDU2OutletSwitchedStatusState[{#SNMPINDEX}].diff()}=1</p><p>Recovery expression: </p> | information |
I have created a very detailed template for a Rack Mounted APC PDU. I spent a considerable amount of time digging through the MIB to obtain all the correct OID numbers pertaining to each Item for the PDU to use with SNMP. The template includes:
I hope you enjoy using this template as much as I have. You can tweak the Interval and History settings within each item per your needs. I have also included HOSTNAME calls in each Trigger to Identify the host that is causing the Trigger.
Chad Hoye
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | public |
Text macro |
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Outlets | <p>-</p> | SNMP agent |
rPDU2Outlet<p>Update: 3600</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
Power Supply Alarm | <p>Indicates a power supply alarm is active when value equals alarm (2)</p> | SNMP agent |
rPDU2DeviceStatusPowerSupplyAlarm.1<p>Update: 10s</p> |
Phase 2 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.2<p>Update: 10s</p> |
Rack Inlet Humidity | <p>The Relative Humidity entering the rack</p> | SNMP agent |
rPDU2SensorTempHumidityStatusRelativeHumidity.1<p>Update: 10s</p> |
Phase 2 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.2<p>Update: 12h</p> |
Peak Power Timestamp | <p>-</p> | SNMP agent |
rPDU2DeviceStatusPeakPowerTimestamp.1<p>Update: 1h</p> |
Power Near Overload Threshold | <p>User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceConfigNearOverloadPowerThreshold.1<p>Update: 12h</p> |
Load State | <p>Indicates the present load status of the Rack PDU.</p> | SNMP agent |
rPDU2DeviceStatusLoadState.1<p>Update: 10s</p> |
Serial Number | <p>-</p> | SNMP agent |
rPDU2IdentSerialNumber.1<p>Update: 12h</p> |
Phase 3 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.3<p>Update: 12h</p> |
Max Phase Current Rating | <p>The maximum current rating, measured in Amps, for the Rack PDU</p> | SNMP agent |
rPDU2DevicePropertiesMaxPhaseCurrentRating.1<p>Update: 1h</p> |
Phase 3 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.3<p>Update: 10s</p> |
Peak Power | <p>The peak power consumption of the Rack PDU load in hundredths of kilowatts.</p> | SNMP agent |
rPDU2DeviceStatusPeakPower.1<p>Update: 10s</p> |
Phase 1 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.1<p>Update: 10s</p> |
Phase 3 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.3<p>Update: 10s</p> |
Power Consumption | <p>The power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceStatusPower.1<p>Update: 10s</p> |
Phase 1 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.1<p>Update: 10s</p> |
Phase 3 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.3<p>Update: 10s</p> |
Phase 2 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.2<p>Update: 12h</p> |
Phase 2 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.2<p>Update: 12h</p> |
Firmware Rev | <p>-</p> | SNMP agent |
rPDU2IdentFirmwareRev.1<p>Update: 12h</p> |
Phase 2 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.2<p>Update: 10s</p> |
Phase 2 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.2<p>Update: 10s</p> |
Phase 2 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.2<p>Update: 10s</p> |
Phase 1 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.1<p>Update: 12h</p> |
System Up Time | <p>-</p> | SNMP agent |
sysUpTime.0<p>Update: 1h</p> |
Phase 1 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.1<p>Update: 12h</p> |
Phase 3 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.3<p>Update: 12h</p> |
Phase 3 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.3<p>Update: 12h</p> |
Location | <p>-</p> | SNMP agent |
rPDU2IdentLocation.1<p>Update: 1h</p> |
Phase 3 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.3<p>Update: 10s</p> |
Phase 1 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.1<p>Update: 12h</p> |
Phase 1 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.1<p>Update: 10s</p> |
Model Number | <p>-</p> | SNMP agent |
rPDU2IdentModelNumber.1<p>Update: 12h</p> |
Phase Status Peak Current Timestamp | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrentTimestamp.1<p>Update: 1h</p> |
Identification Name | <p>-</p> | SNMP agent |
rPDU2IdentName.1<p>Update: 1h</p> |
Phase 1 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.1<p>Update: 12h</p> |
Power Overload Threshold | <p>User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceConfigOverloadPowerThreshold.1<p>Update: 12h</p> |
Total Energy | <p>A user re-settable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.</p> | SNMP agent |
rPDU2DeviceStatusEnergy.1<p>Update: 1h</p> |
Rack Inlet Temp | <p>Temperature of Air entering Rack</p> | SNMP agent |
rPDU2SensorTempHumidityStatusTempF.1<p>Update: 10s</p> |
Outlet $1 Name | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedConfigName[{#SNMPINDEX}]<p>Update: 3600</p><p>LLD</p> |
Outlet $1 Bank | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedPropertiesBank[{#SNMPINDEX}]<p>Update: 86400</p><p>LLD</p> |
Outlet $1 State | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedStatusState[{#SNMPINDEX}]<p>Update: 60</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
Outlet {#SNMPVALUE} State Change | <p>-</p> | <p>Expression: (last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1</p><p>Recovery expression: </p> | information |
Outlet {#SNMPVALUE} State Change (LLD) | <p>-</p> | <p>Expression: (last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1</p><p>Recovery expression: </p> | information |
I have created a very detailed template for a Rack Mounted APC PDU. I spent a considerable amount of time digging through the MIB to obtain all the correct OID numbers pertaining to each Item for the PDU to use with SNMP. The template includes:
I hope you enjoy using this template as much as I have. You can tweak the Interval and History settings within each item per your needs. I have also included HOSTNAME calls in each Trigger to Identify the host that is causing the Trigger.
Chad Hoye
Name | Description | Default | Type |
---|---|---|---|
{$SNMP_COMMUNITY} | <p>-</p> | public |
Text macro |
There are no template links in this template.
Name | Description | Type | Key and additional info |
---|---|---|---|
Outlets | <p>-</p> | SNMP agent |
rPDU2Outlet<p>Update: 3600</p> |
Name | Description | Type | Key and additional info |
---|---|---|---|
Power Supply Alarm | <p>Indicates a power supply alarm is active when value equals alarm (2)</p> | SNMP agent |
rPDU2DeviceStatusPowerSupplyAlarm.1<p>Update: 10s</p> |
Phase 2 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.2<p>Update: 10s</p> |
Rack Inlet Humidity | <p>The Relative Humidity entering the rack</p> | SNMP agent |
rPDU2SensorTempHumidityStatusRelativeHumidity.1<p>Update: 10s</p> |
Phase 2 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.2<p>Update: 12h</p> |
Peak Power Timestamp | <p>-</p> | SNMP agent |
rPDU2DeviceStatusPeakPowerTimestamp.1<p>Update: 1h</p> |
Power Near Overload Threshold | <p>User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceConfigNearOverloadPowerThreshold.1<p>Update: 12h</p> |
Load State | <p>Indicates the present load status of the Rack PDU.</p> | SNMP agent |
rPDU2DeviceStatusLoadState.1<p>Update: 10s</p> |
Serial Number | <p>-</p> | SNMP agent |
rPDU2IdentSerialNumber.1<p>Update: 12h</p> |
Phase 3 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.3<p>Update: 12h</p> |
Max Phase Current Rating | <p>The maximum current rating, measured in Amps, for the Rack PDU</p> | SNMP agent |
rPDU2DevicePropertiesMaxPhaseCurrentRating.1<p>Update: 1h</p> |
Phase 3 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.3<p>Update: 10s</p> |
Peak Power | <p>The peak power consumption of the Rack PDU load in hundredths of kilowatts.</p> | SNMP agent |
rPDU2DeviceStatusPeakPower.1<p>Update: 10s</p> |
Phase 1 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.1<p>Update: 10s</p> |
Phase 3 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.3<p>Update: 10s</p> |
Power Consumption | <p>The power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceStatusPower.1<p>Update: 10s</p> |
Phase 1 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.1<p>Update: 10s</p> |
Phase 3 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.3<p>Update: 10s</p> |
Phase 2 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.2<p>Update: 12h</p> |
Phase 2 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.2<p>Update: 12h</p> |
Firmware Rev | <p>-</p> | SNMP agent |
rPDU2IdentFirmwareRev.1<p>Update: 12h</p> |
Phase 2 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.2<p>Update: 10s</p> |
Phase 2 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.2<p>Update: 10s</p> |
Phase 2 Power | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPower.2<p>Update: 10s</p> |
Phase 1 Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigOverloadThreshold.1<p>Update: 12h</p> |
System Up Time | <p>-</p> | SNMP agent |
sysUpTime.0<p>Update: 1h</p> |
Phase 1 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.1<p>Update: 12h</p> |
Phase 3 Near Overload Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigNearOverloadThreshold.3<p>Update: 12h</p> |
Phase 3 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.3<p>Update: 12h</p> |
Location | <p>-</p> | SNMP agent |
rPDU2IdentLocation.1<p>Update: 1h</p> |
Phase 3 Voltage | <p>-</p> | SNMP agent |
rPDU2PhaseStatusVoltage.3<p>Update: 10s</p> |
Phase 1 Low Load Threshold | <p>-</p> | SNMP agent |
rPDULoadPhaseConfigLowLoadThreshold.1<p>Update: 12h</p> |
Phase 1 Load | <p>-</p> | SNMP agent |
rPDULoadStatusLoad.1<p>Update: 10s</p> |
Model Number | <p>-</p> | SNMP agent |
rPDU2IdentModelNumber.1<p>Update: 12h</p> |
Phase Status Peak Current Timestamp | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrentTimestamp.1<p>Update: 1h</p> |
Identification Name | <p>-</p> | SNMP agent |
rPDU2IdentName.1<p>Update: 1h</p> |
Phase 1 Peak Current | <p>-</p> | SNMP agent |
rPDU2PhaseStatusPeakCurrent.1<p>Update: 12h</p> |
Power Overload Threshold | <p>User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.</p> | SNMP agent |
rPDU2DeviceConfigOverloadPowerThreshold.1<p>Update: 12h</p> |
Total Energy | <p>A user re-settable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.</p> | SNMP agent |
rPDU2DeviceStatusEnergy.1<p>Update: 1h</p> |
Rack Inlet Temp | <p>Temperature of Air entering Rack</p> | SNMP agent |
rPDU2SensorTempHumidityStatusTempF.1<p>Update: 10s</p> |
Outlet $1 Name | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedConfigName[{#SNMPINDEX}]<p>Update: 3600</p><p>LLD</p> |
Outlet $1 Bank | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedPropertiesBank[{#SNMPINDEX}]<p>Update: 86400</p><p>LLD</p> |
Outlet $1 State | <p>-</p> | SNMP agent |
rPDU2OutletSwitchedStatusState[{#SNMPINDEX}]<p>Update: 60</p><p>LLD</p> |
Name | Description | Expression | Priority |
---|---|---|---|
Outlet {#SNMPVALUE} State Change | <p>-</p> | <p>Expression: (last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1</p><p>Recovery expression: </p> | information |
Outlet {#SNMPVALUE} State Change (LLD) | <p>-</p> | <p>Expression: (last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1</p><p>Recovery expression: </p> | information |