Available versions




SNMP APC InRow

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
UPS InRow Rack Inlet Temp <p>The unit rack inlet temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusRackInletTemp<p>Update: 3m</p>
UPS InRow Hardware Revision <p>A character string identifying the unit controller hardware revision.</p> SNMP agent AirirscunitIdentHardwareRevision<p>Update: 1h</p>
UPS InRow Name <p>A character string identifying the unit name.</p> SNMP agent AirirscunitIdentName<p>Update: 1h</p>
UPS InRow Supply Air Temp <p>The unit supply air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSupplyAirTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Return Air High Temp <p>Unit return air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsReturnAirHighTempMetric<p>Update: 1h</p>
UPS InRow Return Air Temp <p>The unit return air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusReturnAirTempMetric<p>Update: 3m</p>
UPS InRow Cond Inlet Temp <p>The unit condenser inlet air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusCondInletTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Supply Air High Temp <p>Unit supply air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsSupplyAirHighTempMetric<p>Update: 1h</p>
UPS InRow Suction Temp <p>The unit suction temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSuctionTempMetric<p>Update: 3m</p>
UPS InRow Superheat Temp <p>The unit superheat temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSuperheatTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Rack Inlet High Temp <p>Unit rack inlet air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsRackInletHighTempMetric<p>Update: 1h</p>
UPS InRow Location <p>A character string identifying the unit location.</p> SNMP agent AirirscunitIdentLocation<p>Update: 1h</p>
UPS InRow Serial Number <p>A character string identifying the unit serial number.</p> SNMP agent AirirscunitIdentSerialNumber<p>Update: 1h</p>
UPS InRow Firmware Revision <p>A character string identifying the unit firmware version.</p> SNMP agent AirirscunitIdentFirmwareRevision<p>Update: 1h</p>
UPS InRow Manufacture Date <p>A character string identifying the unit manufacture date.</p> SNMP agent AirirscunitIdentManufactureDate<p>Update: 1h</p>
UPS InRow Cond Outlet Temp <p>The unit condenser outlet air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusCondOutletTempMetric<p>Update: 3m</p>
UPS InRow Model Number <p>A character string identifying the unit model number.</p> SNMP agent AirirscunitIdentModelNumber<p>Update: 1h</p>

Triggers

There are no triggers in this template.

SNMP APC InRow

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
UPS InRow Serial Number <p>A character string identifying the unit serial number.</p> SNMP agent AirirscunitIdentSerialNumber<p>Update: 1h</p>
UPS InRow Model Number <p>A character string identifying the unit model number.</p> SNMP agent AirirscunitIdentModelNumber<p>Update: 1h</p>
UPS InRow Cond Inlet Temp <p>The unit condenser inlet air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusCondInletTempMetric<p>Update: 3m</p>
UPS InRow Rack Inlet Temp <p>The unit rack inlet temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusRackInletTemp<p>Update: 3m</p>
UPS InRow Suction Temp <p>The unit suction temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSuctionTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Return Air High Temp <p>Unit return air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsReturnAirHighTempMetric<p>Update: 1h</p>
UPS InRow Thresholds Rack Inlet High Temp <p>Unit rack inlet air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsRackInletHighTempMetric<p>Update: 1h</p>
UPS InRow Cond Outlet Temp <p>The unit condenser outlet air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusCondOutletTempMetric<p>Update: 3m</p>
UPS InRow Supply Air Temp <p>The unit supply air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSupplyAirTempMetric<p>Update: 3m</p>
UPS InRow Location <p>A character string identifying the unit location.</p> SNMP agent AirirscunitIdentLocation<p>Update: 1h</p>
UPS InRow Hardware Revision <p>A character string identifying the unit controller hardware revision.</p> SNMP agent AirirscunitIdentHardwareRevision<p>Update: 1h</p>
UPS InRow Firmware Revision <p>A character string identifying the unit firmware version.</p> SNMP agent AirirscunitIdentFirmwareRevision<p>Update: 1h</p>
UPS InRow Return Air Temp <p>The unit return air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusReturnAirTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Supply Air High Temp <p>Unit supply air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsSupplyAirHighTempMetric<p>Update: 1h</p>
UPS InRow Name <p>A character string identifying the unit name.</p> SNMP agent AirirscunitIdentName<p>Update: 1h</p>
UPS InRow Superheat Temp <p>The unit superheat temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSuperheatTempMetric<p>Update: 3m</p>
UPS InRow Manufacture Date <p>A character string identifying the unit manufacture date.</p> SNMP agent AirirscunitIdentManufactureDate<p>Update: 1h</p>

Triggers

There are no triggers in this template.

SNMP APC InRow

Macros used

There are no macros links in this template.

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
UPS InRow Serial Number <p>A character string identifying the unit serial number.</p> SNMP agent AirirscunitIdentSerialNumber<p>Update: 1h</p>
UPS InRow Model Number <p>A character string identifying the unit model number.</p> SNMP agent AirirscunitIdentModelNumber<p>Update: 1h</p>
UPS InRow Cond Inlet Temp <p>The unit condenser inlet air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusCondInletTempMetric<p>Update: 3m</p>
UPS InRow Rack Inlet Temp <p>The unit rack inlet temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusRackInletTemp<p>Update: 3m</p>
UPS InRow Suction Temp <p>The unit suction temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSuctionTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Return Air High Temp <p>Unit return air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsReturnAirHighTempMetric<p>Update: 1h</p>
UPS InRow Thresholds Rack Inlet High Temp <p>Unit rack inlet air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsRackInletHighTempMetric<p>Update: 1h</p>
UPS InRow Cond Outlet Temp <p>The unit condenser outlet air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusCondOutletTempMetric<p>Update: 3m</p>
UPS InRow Supply Air Temp <p>The unit supply air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSupplyAirTempMetric<p>Update: 3m</p>
UPS InRow Location <p>A character string identifying the unit location.</p> SNMP agent AirirscunitIdentLocation<p>Update: 1h</p>
UPS InRow Hardware Revision <p>A character string identifying the unit controller hardware revision.</p> SNMP agent AirirscunitIdentHardwareRevision<p>Update: 1h</p>
UPS InRow Firmware Revision <p>A character string identifying the unit firmware version.</p> SNMP agent AirirscunitIdentFirmwareRevision<p>Update: 1h</p>
UPS InRow Return Air Temp <p>The unit return air temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusReturnAirTempMetric<p>Update: 3m</p>
UPS InRow Thresholds Supply Air High Temp <p>Unit supply air high temperature threshold in tenths of degrees Celsius.</p> SNMP agent AirirscunitThresholdsSupplyAirHighTempMetric<p>Update: 1h</p>
UPS InRow Name <p>A character string identifying the unit name.</p> SNMP agent AirirscunitIdentName<p>Update: 1h</p>
UPS InRow Superheat Temp <p>The unit superheat temperature in tenths of degrees Celsius.</p> SNMP agent AirirscunitStatusSuperheatTempMetric<p>Update: 3m</p>
UPS InRow Manufacture Date <p>A character string identifying the unit manufacture date.</p> SNMP agent AirirscunitIdentManufactureDate<p>Update: 1h</p>

Triggers

There are no triggers in this template.